5-16
Instructions for Use
Rexroth Diax 04 HVE/HVR
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
X11, DC bus connection
hve_X11.fh7
U
V
W
X5
Max.Drehmoment/Torque: U,V,W, =2Nm
L +
L -
X1
DC bus connection X11
Fig. 5-42: Terminal X11
Type
Number of poles
Type of design
terminal block
2
screw terminal for ring
cable lug M5
Fig. 5-43:
Design
Cross section
single-core
[mm²]
Cross section
multi-core
[mm²]
Wire size
in AWG
gauge No.:
--
35
--
Fig. 5-44:
Connection cross section
3 Nm
CAUTION
Risk of damage by interchanging the DC bus
connections L+ and L-
⇒
When connecting the DC bus make sure the polarity
is correct.
If in special cases it is impossible to use the DC bus strands provided to
make the connection, the connection must be made using the shortest
possible twisted wires!
line length:
•
within a drive package
•
between two drive packages
•
HZS application in stand-alone operation
•
max. 2 x 1 m
•
max. 2 x 15 m
•
max. 2 x 30 m
line cross section
min. 10 mm
2
;
but not smaller than cross section of supply feeder
line protection
by circuit breakers in the mains connection
dielectric strength of single strand against ground
≥
750 V
(e.g. strand type - H07)
Fig. 5-45: Lines for DC bus connection
Terminal X11
Design
Connection cross section
Tightening torque
Lines for DC bus connection