Rexroth Diax 04 HVE/HVR
Instructions for Use
5-17
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
X12, Ground connection
hve_X12.fh7
U
V
W
X5
Max.Drehmoment/Torque: U,V,W, =2Nm
L +
L +
X1
grounding
bracket
Fig. 5-46: Terminal X12
Screw terminal
3 Nm
The ground connection to the drive controllers is double:
•
rear panel of device and mounting rail
•
grounding bracket on the front (see figure)
To ensure the connection of the devices to the protective conductor
system, connect the neighboring devices to both sides via the grounding
brackets:
Abb. 5-47: Grounding brackets
X13, Optional choke connection (only HVE)
1L+
2L+
hve_X13.fh7
hve04_X13.fh7
1L+
2L+
HVE02 and HVE03
(jumpered at delivery)
HVE04
(not jumpered at delivery)
Fig. 5-48: Terminal X13
Terminal X12
Design
Tightening torque
Terminal X13