D8024/D10024A
Overview
D8024/D10024A Operation and Installation Guide
50616B
Page 10
© 2002 Radionics
2.1
Specifications
2.1.1
D8024
Operating Voltage
120 VAC, 60 Hz
Operating Current
Control: 325 mA
Polling Circuit: 30 mA / c sensor load
Power Supply
24 VDC Nominal @ 3 A
Notification
Appliance Circuits
(Sounder Outputs)
2 programmable, 1 A/ output max.
2.2 k
Ω
supervised EOL resistor
On-board Relays
(dry contacts)
2 Form “C” contacts rated @ 5 A, 250 VAC max. /relay
Sensor Circuit
Supports 1 or 2 D9067 loop driver modules up to 7,200 ft. (2,195 m) 16
AWG (1.5 mm) per loop. No special wire requirements supports Class
“A” wiring
Maximum Devices
126 per circuit, 2 circuit max.
Sensor Circuit Protection
Power limited, automatic over current protection
Display
2-line by 40-character back lit liquid crystal display
20 LED fire zone indicators
20 LED zone fault indicators
10 LED system indicators
Keyboard
Membrane w/Snap Dome
Alphanumeric 21-key keypad
Dimensions
(H x W x D)
15.5 in. x 15.75 in. x 5.5 in.
(39 cm x 40 cm x 14 cm)
Table 2: D8024 Specifications
2.1.2
D10024A
Operating Voltage
120 VAC Primary
Operating Current
Control: 325 mA
Polling Circuit: 30 mA/c sensor load
Power Supply
24 VDC Nominal at 3 A
4 Programmable Supervised
Indicating Circuits (Output)
1 amp/output max Total Current = 2 A
On-board Relays
2 Form “C” contacts rated at 5 A, 250 VAC max. per relay
Sensor Circuit
2-wire analog addressable circuit to operate w/addressable analog
protocols
Maximum Devices
126 per circuit, 5 circuit max.
Sensor Current
150 mA typical
Sensor Circuit Protection
Short circuit protection on-board (without isolators in circuit)
Display
2-line by 40-character back lit liquid crystal display 40 or 80 LED zone
Fire indicators 40 or 80 LED zone Fault indicators 10 LED System
indicators
Keyboard
Membrane with Snap Dome Alphanumeric 21-key keypad
Printer
40-character remote (optional)
Dimensions
(H x W x D)
20 in. x 16 in. x 6.6 in.
(51 cm x 40.6 cm x 16.8 cm)
Table 3: D10024A Specifications