Event Logic
•
The System event logic allows complex logic sequences to be programmed into the fire panel.
•
The logic modes support both “AND” (coincidence) and “OR” functions on events, together with timers
adjustable in 1 second steps up to 999 seconds.
•
A PC is essential for programming event logic.
•
The “ Logic” display allows any event sequence uploaded from the PC to be inspected on the Panel.
14.1.3
Define Event Outputs
•
All output devices can have two system events directly assigned to them.
•
A relay style device will turn on if either of the assigned events occur.
•
A NAC style device will turn on if the primary event occurs, (Shown as “Event-A”), or will pulse if only the
secondary event occurs (“Shown as Event-B”).
•
The “Define outputs” display option allows the events assignments to be inspected and changed if required.
It strongly recommended that a PC be normally used to define events.
•