D8024/D10024A
Installation
D8024/D10024A Operation and Installation Guide
50616B
Page 16
© 2002 Radionics
•
Pressing the SHIFT key will
show a list of optional
functions or prompt for the
level 2 password. (See
Section 3.3 Enabling Level 2
or Level 3 Access on page
16)
Figure 8: Enable Control Keys?
3.2
Memory Lock
•
To make changes that affect the
configuration of the system, such as
adding detectors, the system memory
must first be unlocked.
•
Open the enclosure door and move the
memory lock switch to the open position.
•
The Memory Lock Switch is located on
the CPU Board.
•
The figure opposite shows the interior of
the D8024 Fire Alarm Control Panel. The
D10024A Fire Alarm Control Panel uses
the same CPU Board and has a similar
arrangement.
Ensure that the Memory Lock Switch is
open prior to performing any
programming.
Ensure that the Memory Lock Switch is
closed before returning the panel to
normal operation.
Memory Lock Switch
Printer Port
Figure 9: Memory Lock Switch Location
3.3
Enabling Level 2 or Level 3 Access
•
To enable Level 2 or Level 3
operation, press the SHIFT
key. The display will then
show:
•
Press the
YES
key and the
display will prompt for entry of
the password.
•
Enter the
4-digit Level 2
password
. The display then
shows the Main Menu of user
options.
•
If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display
showing the system status message. To re-show the menu display, press the
SHIFT
key.
•
If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then
Level 2 access will be automatically canceled. It will be necessary to re-enter the password to re-activate
Level 2 functions.
•
For detailed information on the Level 2 user options, refer to the
D8024/D10024A User Manual (P/N 50618).
3.3.1
Selecting the commissioning option
•
To access the commissioning functions in the panel, press
1
to select the commission option.
•
The display will prompt for entry of the Level 3 password. Enter the Level 3 password using the number
keys and then press ENTER.
•
The display will then show the commissioning menu options.