![Bosch Radionics D10024A Operation And Installation Manual Download Page 47](http://html.mh-extra.com/html/bosch/radionics-d10024a/radionics-d10024a_operation-and-installation-manual_39365047.webp)
D8024/D10024A
Network Options
D8024/D10024A Operation and Installation Guide
© 2002 Radionics
Page 47
50616B
13.0 Network Options
•
Network options define the way in which the panel is configured to operate on a networked system. These
options, such as the panel address, should be checked when a system is first installed, but will rarely need
altering after this time.
•
A summary of the network options for various network configurations is given below. Refer to the
D8024/D10024A Networking Guide (P/N 34377) for further detailed information.
•
Press
3
to select the ‘Network’ option from Page 3 of the commission menus.
•
To change a setting, press either CHANGE or NO and then enter the desired setting. Step on using the YES
key.
13.1
Panel Networks
13.1.1
Network - Panel Network Address
•
The Network Address will have been set when the panel leaves the factory. It may need to be changed,
however, when the panel is installed in a network system. If the panel is not required on a network, then this
address should be set to 1.
•
Each panel should be given a
unique panel address
number.
13.1.2
Standard Network Settings for shared zones
•
The following tables give typical settings for shared zone mini-network system.
Network Option
Option setting
Comments
Panel network-address
number
1..20
Enter slave panel address, i.e. 3.
Quantity of slave processors
0
Number of slaves connected to port C.
Use modem
[TRUE]/[FALSE]
MUST be set to FALSE
Share zones
[TRUE ]
Zones are shared between panels
Peer-to-Peer
[TRUE]
Pass TROUBLE SILENCE, ALARM SILENCE and
RESET key presses back to master.
*Port B Protocol
0
Use default of 0 unless special application interface
System events
[GLOBAL]/[LOCAL ]
Global -
passes system events over network accepts
other network events.
Local -
does not pass events over the network.
Ignores other network events.
NOTE: The zonal fire status is passed over a
shared-zone network regardless of events being
global or local.
Table 14: Slave Panel Network Settings