States of the LED S3 within a period of three seconds
Sercos communication status
–
–
–
–
–
–
–
–
–
–
–
–
No Sercos communication
or or or or or or or or or or or or Communication phase 0
gn or or or or or or or or or or or Communication phase 1
gn or gn or or or or or or or or or Communication phase 2
gn or gn or gn or or or or or or or Communication phase 3
gn gn gn gn gn gn gn gn gn gn gn gn Communication phase 4
or gn or gn or gn or gn or gn or gn Hot-plug phase 0
or gn gn gn gn gn gn gn gn gn gn gn Hot-plug phase 1
or gn or gn gn gn gn gn gn gn gn gn Hot-plug phase 2
gn –
gn –
gn –
gn –
gn –
gn –
Fast forward
→
Loopback
rt
or rt
or rt
or rt
or rt
or rt
or Application error
gn rt
gn rt
gn rt
gn rt
gn rt
gn rt
MST losses
rt
rt
rt
rt
rt
rt
rt
rt
rt
rt
rt
rt
Communication error (C1D)
–
or –
or –
or –
or –
or –
or Identification
rt
–
rt
–
rt
–
rt
–
rt
–
rt
–
Watchdog error
– : Off
or: Orange
gn: Green
rt: Red
Tab. 12-4: Sercos communication status
13 Troubleshooting and debugging
LEDs indicate the operating states of the SafeLogic compact Sercos Gateway.
Errors
Cause
All LEDs off
The external 24 V voltage supply is missing or beyond the specified
operating range.
No Sercos connection at
XFE1 or XFE2
Possible causes:
●
The Sercos cabling (e.g. position of the plug in the RJ45 sockets) is
incorrect.
●
The respective Sercos communication partners are not enabled
●
The parameterization is incorrect (refer to the project planning
manual "Rexroth IndraControl SafeLogic compact Sercos Gateway"
tab. 1-2 "Required and supplementing documentation" on page
Tab. 13-1: Possible error states and causes
For the description of the LED displays, refer to
Bosch Rexroth AG
Troubleshooting and debugging
Sercos Gateway
22/31
DOK-CONTRL-SLC*GW*GS3S-IT03-EN-P
Summary of Contents for R911172765
Page 1: ...IndraControl SafeLogic compact Sercos Gateway Operating Instructions R911338431 Edition 03 ...
Page 30: ...Bosch Rexroth AG Sercos Gateway 26 31 DOK CONTRL SLC GW GS3S IT03 EN P ...
Page 33: ...Sercos Gateway Bosch Rexroth AG DOK CONTRL SLC GW GS3S IT03 EN P 29 31 ...
Page 34: ...Bosch Rexroth AG Sercos Gateway 30 31 DOK CONTRL SLC GW GS3S IT03 EN P ...