132
en | Programming options
PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
6.4
Programming settings
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES:
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control and Communication Units for Mass
Notification Systems, UL2572, certain programming features or options must be limited to
specific values or not used at all as indicated in the following chapters.
The order of the configure topics listed on the start screen is the preferred programming
sequence. See the following chapters.
6.4.1
User accounts
To access the configuration web pages of the webserver, Open Interface and Logging server,
an account is needed. An account consists of a username, a password and an authorization
level. The authorization level defines to which part of the webserver access is granted. Notice:
Initially you have already created an Administrator user account. See
The webserver provides the following authorization levels:
–
Administrators
: Administrators have access to all parts of the webserver including the
User accounts part, Logging Server, Logging Viewer and Open Interface.
–
Installers
: With the exception of the User accounts and Backup and restore parts,
installers have access to all parts of the webserver, Logging Server, Logging Viewer and
Open Interface.
–
Operators
: Operators have access to the Diagnose > version and About sections of the
webserver, Logging Server, Logging Viewer and Open Interface.
Topic
Configure /
programming
Feature or option
Permitted
in UL2572
(Y/N/
required)
Possible settings
Value
Settings
permitted in
UL2572
User accounts
(The user
accounts that
provide access
to the
PRAESENSA
webserver can
be managed.)
Add (user
account)
Required
User name
Enter characters
(5‑16)
5-16
characters
Yes
Authorization level
Selection:
Administrator/
Installer/operator
Administrator
for user
management,
Installer for
configuration
, operator for
normal
operation
Required
Password
Enter characters:
Administrator (8‑64)
Installer and
operator (4‑64)
8-64
characters