98
en | Appendix
FAS-420-TM Aspirating Smoke Detector
F.01U.088.878 | 4.1 | 2010.11
Operation Guide
Bosch Sicherheitssysteme GmbH
8.3
Planning with Air Filter
8.3.1
Without Any Other Pipe Accessories
8.3.2
With water separator
Sensitivity
(% LT/m)
Number of openings
1
2
3
4
5
6
7
8
0.5
A
A
B
B
B
C
C
C
0.6
A
B
B
B
C
C
C
C
0.7
A
B
B
C
C
C
C
C
0.8
A
B
B
C
C
C
C
C
0.9
A
B
C
C
C
C
C
C
1.0
A
B
C
C
C
C
C
C
1.1
B
B
C
C
C
C
C
1.2
B
B
C
C
C
C
1.3
B
C
C
C
C
C
1.4
B
C
C
C
C
1.5
B
C
C
C
C
1.6
B
C
C
C
C
1.7
B
C
C
C
1.8
B
C
C
C
1.9
B
C
C
C
2.0
B
C
C
C
Pipe shape
U
Fan
[V]
1
2
3
4
5
6
7
8
I
≥
9
40
40
40
40
40
U
≥
9
50
50
50
50
50
50
50
50
M
≥
9
50
50
50
50
50
50
50
50
Double U
≥
9
50
50
50
50
50
50
50
50
Pipe shape
U
Fan
[V]
1
2
3
4
5
6
7
8
I
≥
9
40
40
40
U
≥
9
50
50
50
50
50
50
M
≥
9
50
50
50
50
50
50
Double U
≥
9
50
50
50
50
50
50
50
50
Summary of Contents for FAS-420-TM
Page 1: ...FAS 420 TM Aspirating Smoke Detector FAS 420 TM en Operation Guide ...
Page 2: ......
Page 103: ......