en | Planning
FAS-420-TM Aspirating Smoke Detector
F.01U.088.878 | 4.1 | 2010.11
Operation Guide
Bosch Sicherheitssysteme GmbH
3.7
Planning with Single-hole Monitoring
Depending on the pipe configuration, the following system parameters are used to detect a
single air sampling opening or a particular number of obstructed air sampling
openings.Planning is to be carried out according to regulations specified in
Section 3.6 Standard Pipe Planning, page 39
. Additionally, the following limiting values and
opening diameters must be observed. An additional accessory (air filter, condensate
separator etc.) can have an effect on the maximum pipe length.
3.7.1
I-pipe system
1 pipe system
FAS-420-TM
FAS-420-TM-R
FAS-420-TM-RVB
Figure 3.7
I-pipe system for space protection
Min. distance FAS-420-TM – 1st air sampling opening
2 m
Max. distance FAS-420-TM – 1st air sampling opening
20 m
Max. total pipe length per pipe system
–
Pipe Ø 25 mm
40 m
–
Additional pipe Ø 12 mm
5 x 3 m
Max. total pipe length per pipe system for a fan voltage < 10.5 V
–
Pipe Ø 25 mm
30 m
–
Additional pipe Ø 12 mm
5 x 3 m
Min. distance between 2 air sampling openings (d)
4 m
Max. distance between 2 air sampling openings (d)
10 m
Max. number of air sampling openings (n) per pipe system
5 units
I-pipe system
Air sampling
opening
Number of air sampling openings
1
2
3
4
5
Ø of air sampling
openings in mm
a
A
6.8
4.6
4.0
3.4
3.0
B
-
5.0
4.2
3.6
3.2
C
-
-
4.4
3.8
3.4
D
-
-
-
4.0
3.6
E
-
-
-
-
3.8
a
Punch diameter of the aspiration reducing film sheet
A
B
C
D
E
FAS / FCS