50
en | Planning
FAS-420-TM Aspirating Smoke Detector
F.01U.088.878 | 4.1 | 2010.11
Operation Guide
Bosch Sicherheitssysteme GmbH
3.8.2
U-Pipe System - Simplified Planning
3.8.3
U-pipe System - Simplified Planning
1 pipe system
FAS-420-TM
FAS-420-TM-R
FAS-420-TM-RVB
Figure 3.12
U-pipe system, e.g. for equipment protection
Limiting values
Min. distance FAS-420-TM – T-fitting
2 m
Max. distance FAS-420-TM – T-fitting
20 m
Max. branch length
25 m
Max. total pipe length per pipe system
–
Pipe Ø 25 mm
–
Additional pipe Ø 12 mm
50 m
8 x 3 m
Max. total pipe length per pipe system for a fan voltage
< 10.5 V
–
Pipe Ø 25 mm
–
Additional pipe Ø 12 mm
40 m
8 x 3 m
Max. number of air sampling openings (n) per pipe
system
8 units
Min. distance between 2 air sampling openings
0.1 m
Max. distance between 2 air sampling openings
4 m
U-pipe system
Number of air sampling openings
2
4
6
8
Ø of all air sampling openings in
mm
a
6.0
4.2
3.4
3.0
a
Punch diameter of the aspiration reducing film sheet
E
D
C
B
A
10
9
8
7
6
5
4
3
2
1
FAS-420-TM
series
FAS / FCS
1 pipe system
FAS-420-TM
FAS-420-TM-R
FAS-420-TM-RVB
Figure 3.13
U-pipe system, e.g. for equipment protection
d
FAS / FCS
Summary of Contents for FAS-420-TM
Page 1: ...FAS 420 TM Aspirating Smoke Detector FAS 420 TM en Operation Guide ...
Page 2: ......
Page 103: ......