Panel and Area Wide Parameters
EN
| 63
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
L## View Area Stat
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
8
View Area Status (Menu function
only)
View the current arm or disarm status and the not
ready to arm status of all areas within the scope of
the keypad in this area. The user needs arming and
disarming authority.
L## View Memory
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
9
View Event
Memory
[COMMAND][4][0]
View all memory events that occurred since the last
time the system was armed for all areas within the
scope of the keypad in this area.
L## View Point Status
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
10
View Point Status (Menu function
only)
View the current status of all points in the area to
which this keypad is assigned.
L## Walk Test
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
11 Walk
Test
[COMMAND][4][4]
Walk Test all Interior or Perimeter Controlled points in
the area to which this keypad is assigned.
The following features come with the Walk Test
Mode:
Battery powered control panel only. A Battery
Test runs during the whole test to ensure that
the battery capacity is capable of supporting
the full load of the control panel if AC fails.
-
This test includes two-sec Bell Test when
the Walk Test starts.
-
The test ends when all points are tested
or the test times out after 20 min of no
activity.
Local alarm annunciation and event printing;
no reports are sent to the central station
receiver.
D1255 Keypad displays a sequential count,
and text after each point is activated and
restored.
The keypad displays ALL PTS TESTED and
an All Points Tested Event is sent to the
central station receiver (if programmed) when
the last point is tested.
If enabled in Routing, Walk Start and Walk
End Reports are sent to the central station
receiver at the beginning and end of the test.
L## Fire Test
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
12 Fire
Test
[COMMAND][5][8]
Fire Walk Test all 24-hour points in the area where
this keypad is assigned.
One person can perform a Fire Walk Test without
assistance. The following features come with the Fire
Test Mode:
Battery powered control panel only. A Battery
Test runs during the whole test to ensure that
the battery capacity is capable of supporting
the full load of the control panel if AC fails.
-
This test includes a 2-sec Bell Test (Fire
Bell relay) for each Fire point that is
tested.
-
The test ends when all points are tested
or the test times out after 20 min of no
activity.
Local alarm annunciation and event printing;
no reports are sent to the central station
receiver.
Automatic smoke detectors reset for all Fire
points programmed with
P## Resettable
as
Yes
.
D1255 Keypad displays a sequential count
and the text for the point after each point is
activated and restored.
If enabled in Routing, Walk Start and Walk
End Reports are sent to the central station
receiver at the beginning and end of the test.