Schedules (Skeds)
EN
| 108
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Default:
0
Selection:
0 to 24, 28, 29
13
Adjust Time Forward One Hour: This sked function is used to make adjustments to the control
panel’s clock. A typical application is to program this to go into effect at 2:00 AM on the date
that Daylight Saving Time begins (during the springtime). No Time Change Report is sent or
logged, but the new time appears in the next report logged.
No other parameters require input for this option.
14
Adjust Time Backward One Hour:
This sked function is used to make adjustments to the control
panel’s clock. A typical application is to program this to go into effect at 2:00 AM on the date that
Daylight Saving Time ends (during the fall). This function can operate only once in a day, even if
multiple Skeds with this function are programmed. No Time Change Report is sent or logged, but the
new time appears in the next report logged.
There are no other parameters that require input for this option.
S## Cmd Center 1[through 8]
15
Sound Watch Tone at
Command Center
(Keypad): This
function sounds the Watch Tone
at the keypad address
programmed in Parameter 1. The
Watch Tone sounds at all
keypads with the address
programmed. Press [ESC] to
silence the tone.
Sound Watch Tone defines the
keypad address where the Watch
Tone sounds. Enter the specific
address at the
S## Cmd Center
prompt.
Default: Blank
Selection: Yes or No
Enable the sked to beep the keypad
programmed
Yes
.
Yes
Watch tone
sounds at this
keypad.
28
Expanded Off-Normal Test Report:
To generate this event, one or more points must be in an off-
normal state at the time the sked executes. In addition, any system trouble that is active also
generates an Expanded Off-Normal Test Report. Expanded Off-Normal Test Reports include the Off
Normal Test Report Event as well as the supplementary event at the time the report is generated.
The Event Log shows only a Test Report Event.
If none of these conditions exists at the time the sked executes, only a Sked Executed Event is
generated and the Off-Normal Test Report is not sent.
29
Non-Expanded Off-Normal Test Report:
Non-Expanded Off-Normal Test Report Events are only
sent when any point is in the off-normal state from any area, but only sends the Off Normal Test
Report Event. Any system trouble that is active also generates a Non-Expanded Off-Normal Test
Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is
generated and the Non-Expanded Off-Normal Test Report is not sent.
To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use
Sked Function Code 9, Test Report and program it to occur on a daily basis as per AHJ
requirements.