![Bosch D7212GV3 Program Entry Manual Download Page 31](http://html.mh-extra.com/html/bosch/d7212gv3/d7212gv3_program-entry-manual_39294031.webp)
D7212GV3 |
Program Entry Guide | 2.0
Panel and Area Wide Parameters
EN
| 31
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Cancel Report
Default:
No
Selection:
Yes or No
Yes
Send Cancel and Fire Cancel
Reports according to routing.
No
Do not send Cancel and Fire Cancel
Reports.
A Cancel and Fire Cancel Report is created when a
passcode is entered to silence an Alarm Bell or a Fire
Bell before the bell time expires.
For SIA CP-01 Compliance
This prompt must be set to
Yes
.
Call for Service Text
Default:
Refer to the program record sheet
Selection:
Twenty alphanumeric characters
Enter the text to display on a D1260 series keypad
when the control panel is out of service.
2.8 Area
Parameters
This programming module contains three
programming categories: Area Parameters, Bell
Parameters, and Open/Close Options.
2.8.1 Area
Parameters
The D7212GV3 can support up to 4 areas.
A# Area On
Default:
Yes (Area 1 only)
Selection:
Yes or No
Yes Enable
area.
No Disable
area.
Use this program item to enable or disable the area
specified.
Area 1 must be enabled:
System events such as power and
phone supervision do not send a
report correctly if Area 1 is disabled.
When programmed
No
, points
assigned to this area do not generate
events, show at the keypad when
arming and disarming, or send status
reports. All user authority in this area
is turned off while the area is
disabled.
Refer to
Keypad Programming of Area # On and
Area# Account Number
on page 31.
A# Account Number
Default:
0000
Selection:
For Modem or Contact ID (four-
digit account numbers): 0000 to
9999, BBBB to FFFF
For Modem (ten-digit account
numbers): 0000000000 to
9999999999, BBBBBBBBBB to
FFFFFFFFFF
Determines the account number for this area. An
account number must be assigned to each active
area.
Account numbers are used to group areas together.
Each area can have a different account number, or
several areas can share the same account number.
The control panel uses the account number as a
reference for arming and keypad text displays.
Contact ID:
Only the last four digits are sent.
Modem IIIa
2
:
Enter a four-digit or ten-digit number.
Keypad Programming of Area # On and Area#
Account Number
D1255
1.
Refer to
Figure 1
on page 6 to access Keypad
Programming and navigate to the
AREA
PARAMETERS
option. Press [ENT].
2.
The keypad reads
AREA NUM 1 – 32
(1 – 8 for
the D7412GV3).
3.
Enter the area number you wish to configure and
press [ENT]. The current area status shows (for
example, AREA 1 ON: YES).
4.
Press [ENT] to change the area’s status.
5.
Press the [PREV] or [NEXT] button to toggle
between YES and NO, and then press [ENT]
when the desired configuration option shows.
When the keypad reads
PARAMETER SAVED
, your
selection is configured.
6.
When the keypad reads
AREA STATUS,
press
[NEXT] to advance to the
A# ACCT NUMBER
option.
The keypad shows the currently
configured account number.
7.
Press [ENT] to change the account number.
8.
The [PREV] button acts as a [Backspace] key.
The [COMMAND] key cycles though the special
account number characters (B, C, D, E, F);
[NEXT] select the account number character.
9.
Press [ENT] to save the changes.
When the keypad reads
Parameter Saved
, your
selection is configured.