![Bosch D7212GV3 Program Entry Manual Download Page 123](http://html.mh-extra.com/html/bosch/d7212gv3/d7212gv3_program-entry-manual_39294123.webp)
D7212GV3 |
Program Entry Guide | 6.0
AUXPARM
EN
| 123
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
In the above example, if there is a
Communication Trouble Condition on the
DX4020, then the ITS-DX4020-G will poll
at the configured poll rate of the DX4020.
If the poll rate of the DX4020 is set to 5
minutes or faster, there is a possibility of
excessive data usage that may exceed
your data plan with the cellular service
provider. Be sure that any
Communication Trouble events are
addressed as soon as possible.
6.9 Miscellaneous
Fire Summary Sustain
Default:
No
Selection:
Yes or No
Yes Forces
the
Summary Fire
relay
output to remain on after the Alarm
Silence command.
No Allows
Summary Fire
relay output
to be silent when the Fire Alarm Bell
output is silenced and all Fire Points
return to normal.
Use this parameter to set the Summary Fire relay
output to continue or to stop after the Fire Alarm Bell
is silenced or times out. Refer to the
Summary Fire
prompt in
Section 2.12.2 Panel-Wide Relays
on page
72.
Fire Supervision Restoral Type
Default:
0
Selection:
0, 1, 2
0
The control panel sends a FIRE
TROUBLE RESTORE when a Fire
Supervision point restores to normal.
1
The control panel sends a FIRE
ALARM RESTORE when a Fire
Supervision point restores to normal.
2
The control panel sends a FIRE
SUPERVISION RESTORE when a
Fire Supervision point restores to
normal.
Determines how the control panel sends a Fire
Supervision Restoral Event.
The Fire Supervision Restore Event is part
of Fire Events in Routing. If Fire Supervision
Restore Events are needed, simply enable
them in Routing.
Early Ambush Timer
Default:
10 min
Selection:
5 to 30 min
The programmed time is the maximum value of the
Early Ambush Timer. When Early Ambush is set to
Yes
for a specified area (refer to
A# Early Ambush
on
page 42) and the area is disarmed, the user has the
amount of time programmed here to enter a second
code into the keypad.