D6412/D4412 Operation and Installation Guide
Page 42
© 2003 Bosch Security Systems
45349E
D6412/D4412
Off-Board Outputs
10.2.4
Installation
You can install the DX3010 in the enclosure with the panel (see Figure 26) using the mounting hardware supplied with the
DX3010.
DX3010 Side
Mounting Locations
R
Y
G
B
Alrm
+
PO1
L-1
+
-
L-2
Com
L-4
Com
L-3
L-6
Com
L-5
L-8
Com
L-7
T
T1
R1
AUXILIARY
JP1
Installer
JP2-PO1
Select
A
B
R
D6412/D4412 PCB
DX3010
Terminals
Enclosure Wall
Mounting Hardware
(supplied w/DX3010)
Figure 26: DX3010 - Control Panel Enclosure Side Mounting
Alternatively, you can mount the DX3010 remotely in its own D203 enclosure as shown in Figure 27.
Distance from the panel is determined by the total combined wire length of all devices (including keypads) connected to the
panels data terminals. The combined total wire length must not exceed 305 m (1000 ft.) 22 AWG (0.8 mm).
Install the
module in
the D203
housing
Figure 27: Installing the DX3010 in a Remote Enclosure
10.2.5
DX3010 to D6412/D4412 SDI Bus Wiring Connections
Table 13 identifies the SDI bus wiring length requirements.
IMPORTANT
If the DX3010 is to be installed far from the control panel, then the control panel cannot be used to power the
DX3010. An external power supply must be used. See
Figure 29
for external power supply connections.
Power Source
#22 AWG (0.8 mm)
#18 AWG (1.2 mm)
D6412/D4412 to DX3010
D6412/D4412
12. 2 m (40 ft.)
24.2 m (80 ft.)
D6412/D4412 to DX3010
External
Power Supply
305 m (1000 ft.)
610 m (2000 ft.)
External Power Supply to DX3010
12.2 m (40 ft.)
24.4 m (80 ft.)
Table 13: DX3010 Wire Lengths