D6412/D4412 Operation and Installation Guide
D6412/D4412
Page 17
© 2003 Bosch Security Systems
45349E
Installation
Opening the Installer Switch from the closed position resets the panel. The panel resets all its timers, counters, indexes, and
buffers. Any points that restore after a reset is performed do not generate Restoral Reports.
Leaving the Installer Switch in the closed position lets you power up the panel and charge the battery as you install the
detection devices and command centers.
3.5
Finishing the Installation
3.5.1
Earth Ground and Installer Switch
First, make the earth ground connection and close the Installer Switch if you have not already done so.
To reduce the occurrence of false alarms upon toggling of the Installer Switch, the panel ignores all point faults while the
devices stabilize during the setup process. The panel’s start-up process takes approximately 60 sec. to complete. It occurs at
power-up and when the panel resets (Installer Switch OPEN). See Section 3.5.7 Power Up and Section 13.3.10 Exiting the
Installer’s Menu for more information. During this period, a screen showing the panel model number (D6412 or D4412),
firmware revision number, and a “Please Wait...” message appears for approximately 10 seconds.
D6412
Rev
X.XX
Please Wait...
3.5.2
Charge the Battery as You Finish
Connect the battery and then the transformer so that the panel can charge the battery as you finish the installation. See
Section 4.0 Power Supply for instructions.
Self-Diagnostics at Power Up and Reset:
The system performs a series of self-diagnostic tests of its hardware, software, and
program at power up and at reset. They take about 60 sec. to complete. Command centers may display “System Fault” and
sound during the power up and reset interval.
If the panel fails any of the tests, a system trouble message appears at the command centers.
Touch the Earth Ground Terminal First:
To discharge any static charge you may be carrying, always touch the panel’s earth
ground terminal before beginning work on the panel.
3.5.3
Install and Wire Detection Devices
Install and wire detection devices and command centers at their locations throughout the premises.
Do not
make the
connections at the panel end of the wiring yet.
Section 7.0 On-Board Sensor Loops contains instructions for wiring the on-board point locations to detection devices. Section
11.0 Arming Devices contains instructions for wiring the command centers.
Instructions for wiring the off-board point locations are found in the instructions packaged with the point expansion
devices.
3.5.4
Install Modules
1.
Power Down First:
Power down the unit by unplugging the transformer and disconnecting the battery.
Bosch Security Systems recommends powering down the unit when installing modules or when making
wiring connections to the panel.
2.
Install and wire any modules required for your installation as described in the module’s installation
instructions.
Instructions for the DX2010 Point Expansion Module and the DX3010 Output Expansion Module are included in this guide.
See Section 8.0 Off-Board Sensor Loops for DX2010 instructions and Section 10.0 Off-Board Outputs for DX3010 instructions.
3.5.5
Make the Telephone Connections
If you are connecting the panel to a ground start phone system, you need to install a D133/D134 Relay. See Section 6.0
Telephone Connections for complete instructions.
3.5.6
Connect the On-Board Points and Command Centers
Connect the on-board points and command center wiring to the system. See Section 7.0 On-Board Sensor Loops and Section
11.0 Arming Devices for instructions.