D6412/D4412 Operation and Installation Guide
Page 58
© 2003 Bosch Security Systems
45349E
D6412/D4412
Installer’s Keypad and Installer Mode
13.3.10 Exiting the Installer’s Menu
When you are ready to exit the Installer’s Menu and return the system to normal operation, open the Installer’s Switch. The
following screen appears for approximately 10 sec. (note that the panel model number may vary).
D6412
Rev
X.XX
Please Wait...
After the 10-sec. waiting period, the text command center display returns to normal (disarmed, no fault/trouble conditions).
13.3.11 Press [0] Call for Service Details
When end users press [Cmd 42] to display system troubles and a Call for Service condition exists, the system displays
Call
for Service
.
The first line of the display is fixed. The second line is programmable text that can be used to enter the preferred phone
number to use if a call for service must be placed. This number could be the central station’s phone number or a different
number. The second line can also be used to show an instructional message, such as “PRESS 0 TO VIEW.” This message
instructs the user to press the [0] key to view system trouble details.
There is a variety of system conditions that can access the Call for Service display. The exact nature of the trouble is not
shown to the end user because none of the conditions can be serviced by them. These conditions require attention of the
servicing company.
Call for Service Details
Comm Fail, Destination 1 [2]:
System tried to send report to this routing destination but failed. See Appendix A Routing
Dialing Tables in the D6412/D4412 Program Entry Guide (P/N: 45351) for details on the communication failed event.
System battery is low:
Battery connected to the panel fell below 12.1 V.
System battery is missing:
Battery connected to the panel is badly discharged, damaged, or disconnected.
Data bus missing, Device ###:
SDI data bus device set to the address shown in the display (###) is missing or has stopped
responding.
Data bus tamper, Device ###:
Tamper on the SDI data bus device set to the address shown in the display (###) is open.
Data bus reset, Device ###:
SDI data bus device set to the address shown in the display (###) has reset its microprocessor.
Data bus trouble, Device ###:
SDI data bus device set to the address shown in the display (###) is sending a trouble message
to the panel. Troubles are defined per device type. See the instructions for the device shown to learn the exact nature of the
trouble.
Bell supervision fault PO2:
Programmable Output 2 (marked PO2 on the panel) can be programmed as a supervised siren/
speaker. See Outputs in the D6412/D4412 Program Entry Guide (P/N: 45351). When PO2 is programmed for supervision,
disconnecting the siren or speaker generates this fault condition.
RF Rcvr Trouble, Device ###:
Premises RF receiver set to the displayed SDI address (Device ###) is sending a trouble message
to the panel. Troubles are defined per receiver type. See the instructions for the receiver shown to learn the exact nature of the
trouble.
RF Rcvr Jammed, Device ###:
Premises RF receiver set to the displayed SDI address (Device ###) is sending a jammed
message to the panel.