background image

6720850722 (2015/06)

CS 200

14 | Service menu

7.4

Diagnosis

Fig. 9  

Diagnosis menu

The 

Diagnosis

 service menu contains a number of tools for 

diagnosis. Note that the menu items shown will vary depending 
on the heating system.

7.4.1 Function tests

This menu can be used to test active system components 
individually. If 

Enable function tests

 is set to 

Yes

 in this menu, 

the normal heating operation is interrupted in the entire 
system. All settings are saved. The settings in this menu are only 
temporary and revert to the respective default settings as soon 
as the 

Enable function tests

 is set to 

No

 or the 

Function test

 

menu is closed. The available functions and the possible 
settings vary depending on the system installed.

A function test is performed by setting the parameters of the 
listed component accordingly. You can check whether the 
mixer, pump or valve responds appropriately by inspecting the 
behaviour of the corresponding component.

The 

solar pump

 can be tested, for instance:

Off

: The pump stops.

On

: The pump starts.

7.4.2 Monitored values

System settings and measurements are displayed in this menu. 
For example, the system can display whether the maximum 
collector temperature or the current cylinder temperature has 
been reached.

You can also call up detailed information on system parts, e.g. 
the swimming pool. The information and values that are 
provided depend on the system that has been installed. 
Observe the technical documentation for modules and other 
system components.

7.4.3 Fault displays

The current faults and the fault history can be called up in this 
menu.

Table 12   Information in the fault display menu

7.4.4 System information

The software versions of the BUS nodes installed in the system 
can be called up in this menu.

7.4.5 Maintenance

You can add a contact address in this menu. When the solar 
controller displays a fault code, the added address is also 
displayed. The end customer can notify the installer to arrange 
an appointment (

 Chapter 9, page 15).

Table 13   Settings in the Maintenance menu

Contact address

The contact address is automatically displayed to the end user 
in case of a fault.

Entering company name and telephone number

The current cursor position will flash (marked by 

  | 

).

Fig. 10  

Entering a contact address

▶ Turn the rotary control knob to move the cursor.
▶ Press the rotary control knob to activate the input field.
▶ Turn the rotary control knob to enter characters.
▶ Press the Back key when you have finished making entries.
▶ Press the Back key again to return to the next previous 

menu.

0010003114.001

Menu item

Description

Active faults

All current faults that are present in the 
system are displayed here according to 
their severity.

Fault history

The last 20 faults are displayed here, 
sorted in order of the time of occurrence. 
The fault history can be deleted in the 
Reset menu (

 Chapter 7.4.6, 

page 15).

Menu item

Description

Contact address

   "Contact address"

0010003273.001

Summary of Contents for CS 200

Page 1: ...6720850722 2015 06 Installation instructions for installers Solar controller CS 200 0010005426 001 EMS 2 ...

Page 2: ...in the display 7 4 3 Operating the service menu 8 4 4 Overview of the service menu 8 5 Commissioning 8 5 1 Overview of the commissioning steps 9 5 2 General commissioning of the solar controller 9 5 3 Systemcommissioningwiththeconfiguration wizard 9 5 3 1 Commissioning the solar heating system 9 5 3 2 Commissioning the freshwater system 10 5 3 3 Commissioning the transfer station 11 5 4 Additional...

Page 3: ...olar heating systems in domestic or light commercial applications Any other use is considered inappropriate We take no responsibility for damage caused through incorrect use H Installation commissioning and maintenance Installation commissioning and maintenance must only be carried out by a competent person Never install the product in wet rooms Only use genuine spare parts H Electrical work Elect...

Page 4: ...mation in these instructions 2 2 Important information on use CAUTION Risk of injury through scalding If the DHW temperature is set to 60 C discharging unmixed domestic hot water can lead to serious scalding Set the temperature for normal operation to 60 C Do not discharge domestic hot water unmixed Install a mixer Only products from Bosch may be used within the BUS system The installation room mu...

Page 5: ...ature is set to 60 C discharging unmixed domestic hot water can lead to serious scalding Set the temperature for normal operation to 60 C Do not discharge domestic hot water unmixed Install a mixer WARNING Risk to life from electric shock Touching live parts can result in an electric shock Beforeinstallingaccessories Disconnectthepowersupply to the heat source building management system and any ot...

Page 6: ...ries or in a star pattern To avoid inductive interference Make sure all low voltage cables are routed separately from mains voltage cables min clearance 100 mm In the case of external inductive interferences e g from photovoltaic systems use shielded cables e g LIYCY and earth the shield on one side The shield should be connected to the building s earthing system e g to a free earth conductor term...

Page 7: ... change of the temperature displayed in the standard display 4 menu key Opens the main menu hold to open the service menu 5 info key Displays the info menu for information about the current selection 6 Back key Returns to previous menu or discards a value press briefly returns to the standard display hold down 7 Rotary control knob Selects turn and Confirms press 4 2 Overview of the symbols in the...

Page 8: ...ding operating mode Press the rotary control knob to activate the input field for the switching time or the operating mode Turn the rotary control knob to change the setting value Confirming or rejecting the change Rejecting the change Press the rotary control knob to activate the marked entry or to confirm the change Turn the rotary control knob to highlight Continue and press the rotary control ...

Page 9: ...enu and the factory defaults to the current system Perform system commissioning Chapter 5 3 5 3 System commissioning with the configuration wizard ThesolarcontrollerautomaticallyrecogniseswhichBUSnodes e g modules are installed in the system The configuration wizard adjusts the menu and the factory defaults The system analysis may take up to one minute After the configuration wizard has performed ...

Page 10: ...r setting Isthesolarsystemfilledand vented Do you want to start the solar system now Yes No Menu item Start configuration wizard Menu item Question Answer setting Check before starting the configuration wizard Module installed and address set Temperature sensor installed System charged and vented Start the configuration wizard Yes No Operating mode Question Answer setting Which system is installed...

Page 11: ...onlybeswitchedofffor maintenance work for example Disconnect power from the entire system and all BUS nodes After a prolonged power failure or extended period of idleness the date and time may need to be reset All other settings are retained permanently 7 Service menu The menu of the solar controller is adapted to your system automatically Somemenuitemsareonlyavailableifthesystem has been set up a...

Page 12: ...iff heat ex Frost prot temp heat ex Central heating backup Start diff ctrl heat back Stop diff ctrl heat back Max mixer temp CH Mixer runtime CH Solar yield optimisation Gross collector area 1 Type collector array 1 Climate zone Reset solar yield Reset solar optimisation Reset elapsed times Set temp Double Match F Glycol content Transfer Transfer start diff Transfer stop diff Start diff diff ctrll...

Page 13: ...gs for the transfer system 7 3 Settings for freshwater systems If a freshwater system with extended function is installed correspondingmenusandmenuitemsareavailable Themenus of the freshwater system are described in detail in the operating instructions of the used module In the DHW settings menu with all freshwater systems the sub menus listed in Tab 11 are available Table 11 General settings for ...

Page 14: ... depend on the system that has been installed Observe the technical documentation for modules and other system components 7 4 3 Fault displays The current faults and the fault history can be called up in this menu Table 12 Information in the fault display menu 7 4 4 System information The software versions of the BUS nodes installed in the system can be called up in this menu 7 4 5 Maintenance You...

Page 15: ...his function is not performed if the domestic hot water has already reached the set temperature within the last 12 hours due to solar heating The daily heat up starts automatically at the set time according to the time set in the solar controller 9 Troubleshooting Table 16 During installation enter the ID number of the solar controller here A fault in the system is indicated on the display of the ...

Page 16: ...Cause Corrective measure Checkconfiguration setaddress at the module The selected setting requires a solar module Change configuration Check the EMS connecting lead to the solar module for damage BUS voltage at the solar module must be between 12 15 V DC Replace damaged cables Solar module defective Replace the module Fault code sub code cause or fault description A51 6021 Collector temperature se...

Page 17: ...6720850722 2015 06 CS 200 Environmental protection and disposal 17 Batteries must not be disposed together with your household waste Used batteries must be disposed of in local collection systems ...

Page 18: ......

Page 19: ......

Page 20: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...

Reviews: