Electrical connection
19
Condens 7000 WP – 6721842519 (2022/03)
7.3
Overview of plug-in strip
Fig. 23 Overview of plug-in strip
Table 6 Plug-in strip symbols
7.4
Connecting electrical components
All cables from electrical components outside the boiler that are
connected to the plug-in strip must be routed to the inside via the strain
relief.
▶ Connect the connecting leads of the components to the plug-in strip
without tension.
▶ Route the connecting lead through the strain relief.
▶ Position the cable conduit [1].
Symbol
Function
Description
On/Off temperature control (volt free) ▶ Connect an On/Off temperature control. (do not connect 230V directly to these
terminals)
Modulation-controlled control unit and
EMS BUS
▶ Connect modulating temperature controller (EMS bus).
External safety interlock contact (volt
free). This connection contains a link as
standard.
If it is necessary to connect several safety components, e.g. a condensate pump and a
thermal cut out for the underfloor heating system, they must be connected in series. If one
of the safety components are interrupted, the heating load to the wall mounted boiler is
interrupted.
▶ Remove wire link.
▶ Connect safety components (in series).
Attention!
230 V components must only be connected via a relay.
Outside temperature sensor
▶ Connect the outside temperature sensor.
Storage cylinder temperature sensor
▶ Connect cylinder temperature sensor.
Temperature sensor of low loss header ▶ Connect the temperature sensor of a low loss header.
▶ Set the use of the low loss header in the service menu: Settings
>
Hydraulics
>
Low-loss
header.
Function modules
▶ Connect the Bus cable of the function module.
▶ If installed in the boiler, install the function module as described in the instructions (
§
Mains voltage
▶ Connect the 230 V power supply for the function module.
Attention!
The total power consumption of the connected components must not exceed
725 W.
Hot water circulation pump
If a DHW circulation line is used, a secondary circulation pump can be connected.
▶ Connect to the secondary circulation pump.
Mains voltage
Mains plug 230 V
AC
▶ Connect the mains plug, if not pre-assembled (
Cylinder pump
▶ Connect the cylinder primary pump.
Fine-wire fuse of the burner control unit There is a replacement fuse under the cover flap on the burner control unit.