Explanation of symbols and safety instructions
Condens 7000 WP – 6721842519 (2022/03)
4
H
System malfunctions caused by third-party
equipment
This heat source is designed for operation with our
control units.
System malfunctions, malfunctions and defects of
system components resulting from the use of third-
party equipment are excluded from liability.
Service work required to repair the damage will be
invoiced.
H
Danger to life from poisoning by flue gas
There is a danger to life from escaping flue gas.
▶ Ensure that flues and gaskets are not damaged.
H
Danger of death from poisoning by flue gas due
to inadequate combustion
Danger of death due to flue gas leak. If flues are
damaged or leaking, or if you smell flue gas, observe
the following rules.
▶ Close the fuel infeed.
▶ Open doors and windows.
▶ If necessary, warn all residents and leave the
building.
▶ Prevent third parties from entering the building.
▶ Rectify any damage to the flue gas pipe
immediately.
▶ Check the combustion air supply.
▶ Do not cover or reduce the size of ventilation
openings in doors, windows and walls.
▶ Ensure that there is adequate combustion air
supply, including for any appliances installed at a
later date, e.g. extractor fans, kitchen fans or air
conditioning units that discharge air to the outside.
▶ Never operate the device if there is insufficient
combustion air supply.
H
Combustion/room air
▶ Keep the combustion/ambient air free of corrosive
substances (e.g. halogenated hydrocarbons that
contain chlorine or fluorine compounds). This will
help to prevent corrosion.
▶ Keep the combustion air supply free of dust.
H
Installation, commissioning and maintenance
Installation, commissioning and maintenance may be
performed only by an approved contractor.
▶ In the case of open flue operation: ensure that the
installation location meets the ventilation
requirements.
▶ Do not repair, manipulate or deactivate safety-
relevant components.
▶ Only install original spare parts.
▶ Check for gas tightness after working on gas-
carrying components.
H
Handover to the user
When handing over, brief the owner in the operation of
the heating system and about the operating
conditions.
▶ Explain operation – with particular emphasis on all
safety-related actions.
▶ Highlight the following points in particular:
– Point out that modifications or repairs may be
carried out only by an approved contractor.
– To ensure safe and environmentally compatible
operation, an annual inspection, and also
cleaning and maintenance as required, must be
carried out within the specified interval.
▶ Point out the possible consequences (material
damage, personal injury and possible danger to life)
of not carrying out inspection, cleaning and
maintenance correctly, or omitting it altogether.
▶ Draw attention to the dangers associated with
carbon monoxide (CO) and recommend the use of
CO detectors.
▶ Hand over the installation and operating
instructions to the user for safekeeping.
H
Inspection and maintenance interval
To ensure the wall mounted gas condensing boiler
works correctly and safely, the following intervals
must be adhered to:
•
Inspection
: annually,
•
Maintenance
: every 2 years or following a burner
runtime of 4000 hours (depending on which occurs
first).