Installation
Condens 7000 WP – 6721842519 (2022/03)
12
If the amount of fill and top-up water is already greater than the
calculated water volume V
max
:
▶ Use the water treatment as specified in the “Water quality operator's
log”.
If the amount of fill and top-up water is less than the calculated water
volume V
max
:
▶ Purge and clean the heating system if required.
▶ Only use untreated potable water.
▶ Do not use chemical additives (e.g. inhibitors or agents that increase
or reduce the pH), apart from as specified in § 5.3.1.
5.3.1
Water conditioning and treatment
NOTICE
Damage to appliance due to sealing agent in the heating water.
▶ Addition of sealing agent to the heating water is not permitted.
Conditioned water is water that has been softened or desalinated and to
which
no
chemicals have been added. Treated water is unconditioned or
conditioned water to which chemicals have been added.
The following water conditioning and water treatment measures have
been approved for use by Bosch:
Table 4 Additives
▶ For information on concentrations and applications, contact the
supplier of the additive.
5.4
Maximum flow temperature
NOTICE
Too much chloride in the heating water can damage the appliance.
If the chloride content in the heating water exceeds 150 ppm, the boiler
may be damaged if the heating water temperature is higher than 80 °C. If
the maximum flow temperature is set higher than 80 °C, the water
treatment must be adapted in order to reduce the chloride content.
▶ If the chloride content is more than 150 ppm, carry out a water
treatment as described in the supplied "Manual for water quality".
The boiler is supplied with a set maximum flow temperature of 80 °C as
standard. Under standard conditions, this maximum boiler temperature
is sufficient to cover the heating load and also guarantee the service life
of the boiler.
A higher maximum flow temperature may however be required for
certain installations. In these cases, the chloride content of the heating
water must be checked and reduced if necessary.
▶ With the chloride content of the heating water.
▶ If the chloride content is more than 150 ppm, perform water
treatment as described in the supplied "Manual for water quality".
▶ Set the maximum flow temperature to the required value (
p. 25).
▶ Contact the manufacturer for more information. You will find the
relevant addresses on the back of this document.
6
Installation
WARNING
Risk of explosion
▶ Close the gas valve before working on gas-carrying components.
▶ After completing the work, check the tightness of all gas-carrying
components.
6.1
Unpacking the boiler
The packaging material is fully recyclable.
▶ Dispose of the boiler packaging after installing the boiler at a
recycling point.
▶ Remove the outer packaging by setting the boiler upright and pulling
it up and off.
▶ Avoid damaging the connections on the boiler at the top and bottom.
▶ Cover the flue outlet adapter of the boiler during assembly.
6.2
Checking the gas type
▶ Check whether the gas type to be connected to the appliance
corresponds to the gas type specified on the data plate. (
§ 2.9, p.
6 ).
6.3
Setting up the boiler
The boiler can be installed in two ways:
• Installation on a frame (accessory).
• Installation on the wall.
To make full use of the modular design of the system, it is advisable to
install the boiler in combination with the frame.
Installation on the frame (accessory)
WARNING
Physical injury due to tipping of the boiler.
The frame must be securely attached to the floor or wall so that the boiler
cannot tip over.
▶ Use fixing materials that are suitable for the subsurface or wall and
offer a sufficient hold.
▶ Fasten the frame to the floor with the bracket (included).
▶ If drilling in the floor is not permitted fasten the frame to the wall.
▶ Mount the cross bars [1] to the stands [2].
▶ Secure the cross bars with the brackets [3] (included).
▶ Place the frame at the required location in the installation room.
Application
Product name
Max.
concentration
[%]
Demineralisation
Demineralisation/
desalination with mixed
bed cartridges
In accordance with
the supplied
"Manual for water
quality"
Inhibitor/antifreeze
Fernox Alphi 11
40
Antifreeze
Noburst AL
40