Addressing
The address of the board is set using a switch on the board’s
underside (see Equipment Configuration, page 15).
Up to three extension boards (BIS) can be connected to one
AMC2 - depending on that the addresses 1 to 3 can be assigned,
only.
Notice!
When configuring the system, ensure that the order of boards
in the access control software corresponds to the addresses
you set using this switch.
This order of addressing determines the numbering of the
boards’ signals - see Connecting Diagrams, page 48.
Address Signal-No.:
AMC2-8IOE
AMC2-16IOE
1
1/ 01 - 08
1/ 01 - 16
2
2/ 01 - 08
2/ 01 - 16
3
3/ 01 - 08
3/ 01 - 16
Table 4.2: Signals numbering
Connecting Relay Outputs
To operate locks or alarm systems, the AMC2-16IOE has 16 form
C relay outputs. The outputs will be connected to the 3-pin
pluggable screw connectors S6 - 9, S14 - 17, S24 - 27, and S32 -
35 - refer to Connecting Diagrams, page 48.
The AMC2 8I-8O-EXT has the connectors S6 - 9 and S14 - 17,
only.
There are no outputs for the AMC2-16IE.
4.8.1
4.9
AMC2 Extensions
Installing | en
33
Bosch Sicherheitssysteme GmbH
2016-11 | AMC2-16IOE |