Notice!
Risk of damage to equipment
To prevent damage to the relays note the following
specifications.
–
the maximum switching current is 1.25 A
–
the maximum switching voltage is 30 Vdc
–
only ohm resistive load can be connected to the relay
–
inductive loads have to be short circuited using recovery
diodes, see image below. These diodes (1N4004) are
supplied with every AMC2-16IOE package.
–
If you need higher voltage for special applications you can
connect external relays to the outputs. Recommended,
depending on the power supply mode, are the relay types
from the Wieland company:
–
Flare move 12DC1W10A
–
Flare move 24DC1W16A
If using locally manufactured products, please ensure that the
specifications of the product are identical with the those listed
above.
A complete connection diagram of the relay output connectors
is shown in Connecting Diagrams, page 48.