Notice!
Risk of damage to equipment
If excessive force is required to close the front cover then it is
probably incorrectly hooked into the back cover. In such cases
the display ’Dialog’ button in the front cover will be misaligned
and will not function correctly.
Cabling
Notice!
Risk of malfunction
The cables used in the AMC2-16IOE access control system are
not prone to electrical interference. However, you should avoid
routing cables close to heavy load switching cables and
equipment. If this is unavoidable, cross the cable at right angles
every 1 to 2 m (3 to 6 ft) to reduce interference.
Conductor data
With the calculation below you can find out which cable type
must be used. If you connect the power supply and the AMC-
device with the delivered cable set from the enclosure the
calculation is not necessary.
For distances below 25 m (75 ft) use AWG18 conductors
(1mm²). For longer distances, install an additional power supply
close to the AMC2 controller.
Please, calculate the voltage drop by checking the conductor
specifications for characteristic resistance values. The voltage
drop shall not exceed 2 V.
Example:
Length = 100 m/328 ft
U = 12V, I = 1A, maximum U
Drop
= 2V
4.5
4.5.1
AMC2 Extensions
Installing | en
23
Bosch Sicherheitssysteme GmbH
2016-11 | AMC2-16IOE |
Summary of Contents for AMC2-16IE
Page 1: ...AMC2 Extensions AMC2 16IOE 8IOE 16IE en Installation Manual ...
Page 2: ......
Page 46: ...46 en Technical Data AMC2 Extensions 2016 11 AMC2 16IOE Bosch Sicherheitssysteme GmbH ...
Page 47: ...AMC2 Extensions Technical Data en 47 Bosch Sicherheitssysteme GmbH 2016 11 AMC2 16IOE ...
Page 53: ......