i.e. RAWG18 (acc. specs) = 6.385
or 20,948
U
Drop
= 20,948
x 0.1 km x 1A = 2.1V
U
Drop
= 6.385
x 328 ft x 1A = 2.1V
Critical condition! Install the power supply closer to the
controller.
Notice!
These specifications apply to power supply, readers, relay
outputs, and extension interface.
Regarding inputs, specific voltage-drop values need to be taken
into account. Refer to Connecting Analog Input Devices, page
38.