Electrical Connections
5–1
1070 073 825-103 (02.04) GB
5
Electrical Connections
Please note that, with respect to all electrical connections, the terminal con-
nection plans and work instructions provided by the machine manufacturer
shall always be binding!
The system planner is also charged with providing and planning for the inte-
gration and implementation of required components, such as Emergency-
STOP circuits, mains switches, etc. in accordance with current technical
standards and at the highest levels of safety attainable.
CAUTION
Risk of damage to system components caused by insertion or remo-
val of plug connectors on energized circuits!
Connections must be made only while the system is switched off.
Observe the following to prevent malfunction:
D
Provide for isolated 24 VDC and 0 V terminal strips inside the control ca-
binet. With regard to cable routing, maintain a minimum distance of 10
cm from all power cables.
D
Connect the CPS21and other industrial components (e.g. CNC, PLC) in
such a way that they are always switched on simultaneously.