P aram eter s
4
User instructions. DGM speed regulator
120
4,190 / 4,210
Relay x function
Unit: whole
Relation with
the parameter:
4,191 / 4,211
4,192 / 4,212
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
51
Def.:
0
Selection of the process quantity on which the output must be switched.
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
50
51
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Continued table
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Ready to start operating (network power supply ON,
no HW enabling, the motor is stopped)
Ready (network power supply ON, HW enabling set,
the motor is stopped)
Operation (network power supply ON, HW enabling set,
the motor is operating)
Ready to start ope Ready
Ready to start ope Ready + Operation
Ready + Operation
Motor power
Torque
Fieldbus
Analog input 1
Analog input 2
PID reference value
Actual PID value
STO channel 1
STO channel 2
Frequency reference value after ramp
Frequency reference value
Actual PID value
Actual frequency value
Absolute torque value
Absolute frequency reference value after ramp
Absolute frequency reference value
Instantaneous absolute number of revs value
Active motor current limit
Technical-actual comparison (Para. 6.070
– 6.071)