P aram eter s
4
User instructions. DGM speed regulator
109
3,069
Fixed PID reference model
Unit: whole
Relation with
the parameter:
1,100
from 3.062 to
3.068
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
2
Def.:
0
Selection of the digital inputs used for the fixed frequencies
0 = Digital In 1
1 = Digital In 1, 2
2 = Digital In 1, 2, 3
(Fixed reference value PID 1) (3.062)
(Fixed reference value PID 1 - 3)
(from 3.062 to 3.064)
(Fixed reference value PID 1 - 7)
(from 3.062 to 3.068)
3,070
PID standby time
Unit: s
Relation with
the parameter:
1,020
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
10000
Def.:
0
If the speed regulator proceeds for the set time with its minimum frequency
(parameter 1.020), the motor is stopped (0 Hz); see also chap. 5.2.1
Explanation of the operating modes/PID process regulation.
0 = deactivated
> 0 = wait time until activation of the standby function
3,071
PID standby hysteresis
Unit: %
Relation with
the parameter:
3,060
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
50
Def.:
0
Wakeup condition for the PID regulator from the standby function.
When the regulation difference is greater than the value set in %, regulation
restarts; see also the PID regulator operating modes.