P aram eter s
4
User instructions. DGM speed regulator
108
3,060
Instantaneous PID value
Unit: whole
Relation with
the parameter:
1,100
1,130
3,061
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
3
Def.:
0
Selection of the input source, from which the actual value is read for the PID
process regulator:
0 = Analog input 1
1 = Analog input 2
2 = DGM Soft-PLC
3 = Fieldbus (fixed input quantity specific for the customer)
3,061
PID inversion
Unit: whole
Relation with
the parameter:
3,060
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
1
Def.:
0
The source of the actual value (parameter 3.060) is inverted
0 = deactivated
1 = activated
from 3.062 to
3.068
PID fixed reference values
Unit: %
Relation with
the parameter:
1,130
3,069
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
100
Def.:
0
PID fixed reference values that must be output based on the connection model
to the digital inputs 1
– 3 set in parameter 3.069 (the selection must be made in
parameter 1.130).