INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
12
Parameter
name
Description Range
Intrusion/
Fire
Delay
The delay for transitions from
“ENTRY ALARM” to “INTRUSION
ALARM” or from “FIRE
PREALARM” to “FIRE ALARM”
from 0 to 254 s
255 means Off (don’t transit
“Fire Alarm” or “Intrusion Alarm”
after one detector
having actuated)
Arming
Delay
The time interval between having
received arming command and
loop transition to the “Armed” status
from 0 to 255 s
Loop Analy-
sis Delay af-
ter Reset
The pause before alarm loop analy-
sis having begun after power dump;
it is necessary for
transient completion
from 1 to 63 s
Relay 1
Control Delay
Relay 2
Control Delay
Relay 3
Control Delay
Relay 4
Control Delay
Relay 5
Control Delay
Relay switching on/off delay after a
particular loop status having
changed
from 0 to 255 sec
Non-
disarming
The loop cannot be disarmed by
any way
On/Off
Auto Rearm-
ing When
Disarmed
Auto transition from “ARM FAILED”
to “ARMED” when loop having re-
covered
On/Off
Auto Rearm-
ing When
Fire/Alarm
Auto transition from “FIRE”,
“INTRUSION ALARM” or “SILENT
ALARM” to “ARM DELAY” when
loop having recovered. The recov-
ering time is equal to the “Intru-
sion/Fire Delay” parameter
multiplied by 15
On/Off
Disarmed
Loop Control
To monitor and transmit the dis-
armed loop resistance changes (is
its normal or not) via RS-485
On/Off
Fire Loop
requery
blocking
Don’t repeat the 1 or 2 fire loop type
status request
On/Off