INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
6
mended to use RIP-12 or RIP-24 uninterruptible power supplies manufac-
tured by NVP BOLID Company.
The device is to be mounted inside the premises and is destined for
clock round duration.
The device must not be used in aggressive medium or dust condition,
or in dangerous space. The device construction design provides the
ingress protection rating in accordance with IP20.
The device is intended to be used under the following ambient condi-
tions:
- operating temperatures from 243 to 323
К
(from
−
30 to +50
°
С
)
- relative humidity up to 98% non-condensing
- vibration load from 1 to 35 Hz, with maximum acceleration 0,5 g
The weight is no more than 0,5 kg, with overall dimensions being
equal to 370×190×38 mm.
The device average mean life is 20 000 hours.
The average operating life is 10 years.
The device uptime after power-on does not exceed 3 seconds pro-
vided at least one device input is supplied by no less than 11V.
2 SPECIFICATIONS
The maximum number of the alarm loops to be connected to the de-
vice is 20.
The number of switching circuits is 5.
The number of input circuits is 26 (see the Appendix C) among them
- alarm loop circuits from 1 to 20
- identifier reader circuit
- RS-485 interface (A and B leads)
- relay 4 and relay 5 controlled output circuits
- power supply inputs
The number of outputs is 7 (see the Appendix C) including
- 3 relay outputs (relay 1, relay 2, relay 3) of “dry contact” type for
switching with the maximum voltage and current up to 28V/2 A or
up to 80V/50 mA
- relay 4 and relay 5 outputs with open and short failure control and
the maximum voltage/current up to 28V/0,5 A
- “
Инд
.
К
” and “
Инд
.
З
” outputs for external dichromatic reader indi-
cator control,
with directly connected LED current being restricted
up to 10 mA. The quit options for LED are 5V/10mA.