4.2 Electrical installation
If the product is not powered using the POE option:
-
Terminal block
[A]
is the power input for K
ELIO
P
RIO
.
-
First turn off the circuit breaker/disconnection switch concerned
-
Connect the power to terminal block
[A]
using a cable with a cross-section of 2.5
mm²,
stripped over 5
mm (
LIVE
/
NEUTRAL
), onto the rear connector on the terminal (110-230
V
AC
–
50/60
Hz).
-
Secure the two wires close to the 2-pin terminal block, using one of the clamping collars
provided.
-
Connect the IT network cable to the RJ45 socket.
If the product is powered using the POE option:
-
With POE option, K
ELIO
P
RIO
is powered only by the Ethernet cable (terminal block
[C]
).
There is therefore no terminal block
[A]
present on the K
ELIO
P
RIO
terminal.
-
Voltage supplied by the POE switch for the terminal if using the POE option:
IEEE 802.3af - 12.95
W - category 3
-
Connect the bell relay if necessary. To do this,
connect the contacts for terminal block
[B]
of
the relay (230
V
AC
50/60
Hz, 1
A
max
). First turn
off the circuit breaker/disconnecting switch
concerned, then connect the cables onto the
terminal block (0.5 to 1.5
mm² max cross-
section, stripped over a length of 5
mm). Secure
the two wires closest to the 2-pin terminal
block, using one of the clamping collars
provided.
[B]
Clamping
collar
[B]
[A]
[C]