16
Shenyang Bluelight Automatic Technology Co., Ltd.
BL6-DU20PX series Integrated Door Motor Controller User Manual
5.2
Function Parameter explanation
5.2.1
Function List group
Press PRG key, then press UP/DOWN key to roll all function group, the detail information is
shown as follow.
Chart 5.1 Function Group List
Function
Group No.
Name
F0
Basic Function Parameters
F1
Motor Parameters
F2
Performance Control Parameters
F3
Door-open Running Parameters
F4
Door-close Running Parameters
F5
Door -control Auxiliary Parameters
F6
Distance Control Parameters
F7
I/O Terminal Function Parameters
F8
Car Top Board Function Parameters
F9
Demonstrates Running Parameters
FA
Fault Display Parameters
5.2.2
Function Detail List
Note: For synchronous motor application, partial factory default setting of function codes is
different from the factory default setting list below.
C
HART
5.2
F
UNCTION
D
ETAIL
L
IST
Function
Code
Name
Setting Range
Min Unit
Factory
Default
Setting
Group F0 Basic Function Parameters
F000
Control Mode
0: Close-loop Vector Control
1:V/F Open loop Running
1
1
F001
Door-control Mode
0: Motor Continuous Duty
1: Speed Control Mode
2: Distance Control Mode
1
1
F002
Instruction Source
0: Door Motor Controller Terminal
Control Mode
1: Operation Panel Control Mode
2: SYLG Integrated Control Mode
(not available for S type)3: Door Motor
Controller Automatic Demonstration
Mode
1
0
F003
Panel Speed Slope
0.00Hz~F104
0.01Hz
0.50Hz
F004
Low-speed Setting
0.00Hz~20.00Hz
0.01Hz
1.00Hz
F005
Carrier Frequency
5.00Hz~12.0kHz
0.1kHz
8.0kHz