To Enable Frequency Output:
1
Open the
App Drawer
2
Select
Outputs
3
Select
Frequency Output
4
Enable
Frequency Output
5
Set
Desired Values
6
Confirm by pressing
Save
9.2
Frequency Output
This output sends a configurable high speed frequency signal. This feature can be used to
control other pumps (in sync / proportionally), data logging systems, and other external
devices for plant automation.
Four points on the slope must be defined:
1) a low Hz value
2) an output rate at the low Hz value
3) a high Hz value
4) an output rate at the high Hz value
Default settings:
0 Frequency (Hz) = 0 percent motor speed
1000 Frequency (Hz) = 100 percent motor speed
Page 31
®
FLEXFLO M4
9.0
Output Setup
Option: Stop the pump and select the graph icon to easily adjust sliders to desired settings
Confirm by pressing “Save”
To Enable 4-20mA Output:
1
Open the
App Drawer
2
Select
Outputs
3
Select
4-20mA Output
4
Enable
4-20mA Output
5
Set desired values for the four
points that is required.
6
Confirm by pressing
Save
9.1
Set 4-20mA Output
This output sends a configurable 4-20mA. This feature can be used to control other pumps (in
sync / proportionally), data logging systems, and other external devices for plant automation.
Four points on the slope must be defined:
1) a low mA value
2) an output rate at the low mA value
3) a high mA value
4) an output rate at the high mA value
Default settings:
4mA = 0 percent motor speed
20mA = 100 percent motor speed
®
FLEXFLO M4
9.0
Output Setup
Page 30
Option: Stop the pump and select the graph icon to easily adjust sliders to desired settings
Confirm by pressing “Save”