Battery acid is corrosive. Avoid spilling on skin or 

 

clothing. Eye protection MUST be worn when 

 

handling the battery.

 

A check valve MUST be used on the primary 

 

and back-up sump discharge.

 

A ground fault circuit interrupter is required. 

 

This pump MUST only be used to pump clear 

 

water. This pump is NOT designed to handle 

effluent, salt water, brine, laundry discharge, or any other application 

which MAY contain caustic chemicals and/or foreign materials. Pump 

damage MAY occur if used in these applications and WILL void warranty.

Specifications

 

 

Construction

Description 

The 12 Volt Advanced Notification System includes a DC back-

up sump pump, an electronic controller with digital display, and 

an auto-dialer. Optimal back-up power is supplied by a 12 volt 

battery (not included). The system is designed for home sump 

applications. When an electrical power outage occurs, the 

electronic controller automatically switches the sump pump to 

battery power.  Power loss will initiate a phone call via the auto- 

dialer to the phone number(s) entered by the homeowner. With 

a 24-hour monitor and a predetermined full system check, the 

system tells you it’s status via a digital display and alerts you to 

potential problems with an audible horn and phone call.  

 

Unpacking

Inspect this unit before it is used. Occasionally, products are 

damaged during shipment. If the pump or components are 

damaged, contact customer service at 888.636.6628.

Safety Guidelines

To help recognize this information, observe the following signal 

words/hazard classifications. 

 

This is the safety alert symbol. It is used to alert you to  

 

 

potential bodily injury hazards. Obey all safety messages that  

 

follow this symbol to avoid possible harm.

 

Danger indicates an imminently hazardous 

  situation which, if NOT avoided, WILL result  

 

in death or serious injury.

 

Warning indicates a potentially hazardous 

  situation which, if NOT avoided, COULD  

 

 

result in death or serious injury.

 

Caution indicates a potentially hazardous 

  situation which, if NOT avoided, MAY result   

 

in minor or moderate injury.

 

Notice indicates important information, that if 

  NOT followed, MAY cause damage to equipment.

General Safety Information

 

This pump is NOT rated for use with flammable/ 

 

combustible liquids vapors or dusts.  

Do NOT use to pump flammable/combustible liquids vapors 

or dusts. Do NOT use in a flammable and/or explosive 

atmosphere. Pump SHOULD be used to pump clear water 

ONLY. Failure to follow these instructions WILL result in bodily 

injury or death.
 

Electric shock hazard. Disconnect 

 

power before servicing. Apply a fixed 

lock or tag to prevent unexpected application of power.
 
 

Electric shock hazard. DO NOT walk    

 

on wet floor until power is disconnected. Use a 

licensed electrician to perform service in accordance with the National 

Electrical Code and all local codes.

CALIFORNIA PROPOSITION 65

 

This product or its power cord MAY contain 

 

chemicals, including lead, known to the 

State of California to cause cancer and birth defects or other 

reproductive harm. Wash hands after handling. 

 

Explosion hazard. Smoking and open flames 

 

prohibited. Battery recharging and 

connections MUST be performed in a well ventilated area.

Power Supply Requirements ......120 V, 60 Hz 

Motor ..........................................12 V DC Motor 

Pump Dimensions ......................11 in. high x 8 3/4 in. base

Motor Housing ........................... 

Impeller ...................................... 

Shaft .......................................... 

Discharge ..................................  

Float Switch .............................. 

NEVER allow children to use pump.

 

Chemical hazard. If battery acid contacts  

 

your eyes, immediately flush eyes with 

copious amounts of clean, tepid water for at least 30 minutes. Seek 

medical attention.

Battery Information

The system is designed to operate most efficiently with a 

deep cycle, sealed lead (Pb) acid (SLA) battery. A deep cycle 

marine battery can also be used. Sealed lead acid batteries cost 

slightly more, but they can last longer than a wet cell battery and 

are maintenance free. The oversize battery case (included) will 

accomodate one 12 Volt battery up to a 27-frame size. Use a new 

battery. Chart 1 illustrates the expected performance with various 

battery combinations. Do not use batteries rated below 40 amp 

hours. Be certain that the area around the battery is well ventilated. 

Before servicing the battery, blow away gasses by waving a piece 

of cardboard near the battery. An assistant should be present or 

close enough to come to your aid in the event of an emergency. 

Have a reliable source of fresh water and soap nearby in case 

battery acid contacts clothing, skin or eyes. Wear eye and clothing 

protection when working around lead acid batteries. Avoid touching 

your eyes when working around lead acid batteries.

Thermoplastic 

Thermoplastic 

Stainless Steel 

1-1/2 in. NPT 

Dual Reed

Please read and save these instructions. This manual contains important Safety Warnings and Operating Instructions. You will need to refer 

to it before attempting any application or maintenance. Always keep this manual with the unit so that it will be easily accessible. Failure to 

read and follow these warnings and instructions could result in property damage, serious injury, or death.

3

DF12VSM

www.blueangelpumps.com

Summary of Contents for DF12VSM

Page 1: ...es not include 12 Volt DC deep cycle battery phone jack phone line pipe and necessary fittings Float Switch Security DC Pump Requires active telephone land line service STEP 2 DISCONNECT POWER If the...

Page 2: ...Notes 2 Operating Instructions and Parts Manual www blueangelpumps com...

Page 3: ...lure to follow these instructions WILL result in bodily injury or death Electric shock hazard Disconnect power before servicing Apply a fixed lock or tag to prevent unexpected application of power Ele...

Page 4: ...low the pump or check valve to be removed easily for servicing 8 Check valve is recommended for effective operation of system The remainder of the discharge pipe installation will vary depending on in...

Page 5: ...etal pipe is required for permanent installation 9 Glue a 45 elbow to the short pipe on the Back Up DC Pump Glue a Y adapter to the short pipe on the existing pump as shown in illustration for Method...

Page 6: ...negative terminal of the battery The display should be lit up at this time If connected improperly an alarm will sound until corrected 4 Plug the pump and float switch connectors into the 12 Volt Adva...

Page 7: ...umber hit ENTER then select the TEST option The system will immediately dial the desired phone number Upon answering the unit will play the following message This is a test of the back up system It wi...

Page 8: ...cond time within three minutes The System keeps track of all the rings from the previous calls accumulates them until the total ring count matches its ring count number 5 or 10 and then it will answer...

Page 9: ...determine the number of devices that may be connected to a telephone line Excessive REN s on a telephone line may result in the devices not ringing in response to an incoming call In most but not all...

Page 10: ...ber at alarm location let ring three 3 times hang up 2 Make a second call to the System within 3 minutes the System will answer on the second ring 3 rings 2 rings System answers on fifth 5th ring 3 Li...

Page 11: ...place if low or defective 5 Check to make sure the back up pump is not air locked Locate the vent hole inspect and clear the hole using a pipe cleaner Pump Cycles Too Frequently 1 Check valve problem...

Page 12: ...allow limitations on how long an implied warranty lasts or do not allow the exclusions or limitations of incidental or consequential damages so the above lim i ta tions might not apply to you This li...

Page 13: ...Interrupteur flotteur S curit Pompe c c Requiert un service de ligne terrestre t l phonique actif TAPE 2 METTRE HORS TENSION Si la source de courant n est pas visible verrouiller en position ouverte a...

Page 14: ...Remarques 14 Fr Instructions d Utilisation et Manuel de Pi ces www blueangelpumps com...

Page 15: ...que NE PAS marcher sur un sol mouill avant que le courant ne soit coup Faire appel un lectricien agr pour effectuer l entretien conform ment au Code national de l lectricit et aux codes locaux PROPOSI...

Page 16: ...ser des pratiques de plomberie s res pour acheminer le tuyau de d charge vers un mur ext rieur par le chemin le plus court R duire le nombre de coudes au maximum dans la mesure o qu ils r duisent le d...

Page 17: ...er un coude de 45 au tuyau court de la pompe de secours c c Coller un adaptateur en Y au tuyau court de la pompe existante comme indiqu sur l illustration de la m thode 2 10 Coller une section courte...

Page 18: ...de la batterie puis connecter le fil noir sur la borne n gative de la batterie L affichage devrait alors s allumer En cas de branchement incorrect une alarme se d clenche jusqu ce que le probl me soit...

Page 19: ...minuteries et toutes les erreurs sont effac es de la m moire du syst me maintenir le bouton RESET r initialisation enfonc pendant au moins 3 5 secondes 2 Appuyer sur le bouton MENU suivi de l option...

Page 20: ...RIE VOCALE EST INSTALL SUR LA M ME LIGNE T L PHONIQUE Pour annuler la s quence d appel d alarme sortant suivre les tapes suivantes TAPES SUIVRE 1 Appeler le syst me le num ro de t l phone du site de l...

Page 21: ...dant lorsqu un avis pr alable n est pas possible la compagnie de t l phone avisera le client d s que possible En outre vous serez inform de votre droit d poser une plainte aupr s de la FCC si vous le...

Page 22: ...g e 60 Batterie charg e 40 Batterie charg e 20 Batterie d charg e tat de la batterie sujet caution APPELT L PHONIQUE ALARME SONORE SIGNALDU SYST ME DE S CURIT Inverser la polarit Figure 6 Tableau des...

Page 23: ...terie faible ou d fectueuse 3 Interrupteur flotteur coinc 4 Fusible d fectueux ou grill 1 V rifier toutes les connexions 2 V rifier la batterie et la remplacer si elle est faible ou d fectueuse 3 S as...

Page 24: ...site de l alarme laisser sonner trois 3 sonneries puis raccrocher 2 Appeler le syst me une seconde fois dans les 3 minutes qui suivent le syst me r pondra au bout e deux sonneries 3 2 sonneries le sys...

Page 25: ...clusion ou la limitation des dommages accessoires ou indirects en cons quence les limitations pr c dentes peuvent ne pas s appliquer tous les cas Cette garantie limit e vous conf re des droits juridiq...

Page 26: ...dor Seguridad Bomba CC Requiere un servicio de tel fono de l nea activado PASO 2 DESCONECTE LA ENERG A Si la protecci n de desconexi n no est a la vista tr nquela en la posici n abierta y etiqu tela p...

Page 27: ...Notas 27 Sp DF12VSM www blueangelpumps com...

Page 28: ...u cable de corriente PUEDEN contener qu micos incluido plomo que son conocidos por el Estado de California como causantes de c ncer y defectos de nacimiento u otros da os reproductivos L vese las mano...

Page 29: ...n para un funcionamiento eficaz del sistema El resto de la instalaci n de la tuber a de descarga variar dependiendo de las circunstancias individuales Dirija la tuber a de descarga hacia una pared ex...

Page 30: ...segunda bomba 9 Pegue un codo de 45 al tubo corto en la bomba de respaldo de CC Pegue un adaptador en Y al tubo corto en la bomba existente como se muestra en la ilustraci n del M todo 2 10 Pegue una...

Page 31: ...tiva de la bater a La pantalla debe iluminarse en este momento Si se conecta de forma incorrecta sonar una alarma hasta que se corrija 4 Enchufe la bomba y los conectores del interruptor de flotador e...

Page 32: ...l nea telef nica est conectada y que la Home Screen pantalla de inicio no tenga mensajes de error 2 Presione el bot n MENU men seguido de la opci n Phone Setup configuraci n del tel fono 3 Despl cese...

Page 33: ...NTESTADORA AUTOM TICA CORREO DE VOZ EN LA MISMA L NEA TELEF NICA Para cancelar la secuencia de llamadas de alarma haga lo siguiente PASOS QUE DEBE REALIZAR 1 Realice la llamada al Sistema n mero de te...

Page 34: ...E LA RED TELEF NICA Si este Sistema causa da o a la red telef nica la compa a telef nica le notificar con anticipaci n que puede ser necesaria la suspensi n temporal del servicio Pero si el aviso con...

Page 35: ...lente El motor zumba pero la bomba no funciona 1 Bater a defectuosa 2 El impulsor est bloqueado 1 Verifique la bater a y reempl cela si el flujo es bajo o defectuoso 2 Desconecte la bomba retire la re...

Page 36: ...cionamiento de menos de 1 hora 1 Corte de energ a 2 Corte de energ a extendido 1 Notifique a la compa a de servicios p blicos 2 Prepare una bater a de repuesto Cambie la bater a 1 La bater a tiene poc...

Page 37: ...est configurado a 5 repiques 1 Haga una llamada al Sistema n mero de tel fono de la ubicaci n de la alarma deje sonar 3 tres veces cuelgue 2 Realice una segunda llamada al Sistema en 3 minutos el Sist...

Page 38: ...as garant as impl citas o no permiten las exclusiones o limitaciones de da os incidentales o consecuentes de manera que las limitaciones mencionadas anteriormente pueden no aplicarse en su caso Esta g...

Page 39: ...Notes Remarques Notas 39 Sp DF12VSM www blueangelpumps com...

Page 40: ...Notes Remarques Notas 40 Sp Manuel de Instrucciones y Lista de Piezas www blueangelpumps com...

Reviews: