G:\InDATA\manuals\OM-1607 E V1.02
November 19, 2012
Page 12
TORINO II Insert 1607
INSTALLATION INSTRUCTIONS cont.
The exhaust and air intake pipe must be securely fastened to the appliance and terminal and all joints must be
secured using a minimum of 3 screws evenly spaced around the pipe.
Approximately 1” from the end of the 3” appliance exhaust pipe outlet at the appliance air intake pipe and at the
3” terminal connections apply a bead of Mil Pac or other high heat silicone 1/4” wide. Slide the 3” pipe onto the
appliance and secure with 3 screws evenly spaced to the outlet.
Exhaust
Air inlet
3” Flex
Fig. 6
Self Tapping
Screw
Mill Pack
Sealant
Some general venting rules for best venting
performance:
1. Observe local code restrictions, if any,
regarding the installation of this type of
gas appliance.
2. Terminate the vent with a suitable vent
termination.
When installed in accordance with the
manufacturer’s instructions the combustion
air supply will be in the same pressure zone as
the vent outlet.
This direct vent appliance must be
installed using an approved venting
system. All vent pipe joints must
be sealed with a high temperature
sealant in order to meet the ANSI/
CSA leakage limit standards.
VENT TERMINAL CLEARANCES
Fig. 8
Consult local codes for minimum vent cap
height above the roof (X), vent must be a
minimum of 2’ from any wall.
Exhaust
Connector
Intake
Connector
Fig. 7 Vent Connectors