Configuring the Action(s)
Type of Actions:
For the defined event, you can choose and configure following actions:
Set Outputs
NOTE:
This type of Action only appears if:
your device has own power outlets or has access to power outlets of connected xBus Peripheral Units.
your device has access to Relay Outputs of connected xBus Peripheral Units.
you have created interface associations through Settings/Associations.
Select this checkbox and choose in the corresponding drop-down list the Output to use for this Rule.
Each Power Outlet can be switched to On, Off, or Restarted.
If you choose “Restart” you can also define a Restart delay to be between 0 and 3,600 seconds.
If you choose 0 seconds for the delay, the delay will be the one defined in the Peripherals page, accessible through
Settings/Peripherals/Edit.
If you choose a delay other than 0, this delay will replace the one defined in the Peripherals page, accessible through
Settings/Peripherals/Edit.
Each Relay Output can be switched to Open, Close, Pulse Open, or Pulse Close.
If you choose Pulse open or Pulse close, you can also define a delay to be between 0 and 3,600 seconds.
If you choose 0 seconds for the delay, the delay will be the one defined in the Peripherals page, accessible through Settings/
Peripherals/Edit.
If you choose a delay other than 0, this delay will replace the one defined Peripherals page, accessible through Settings/Peripherals/
Edit.
Rule to cancel
This type of Action only appears if you already have created a rule that you want to cancel.
Select this checkbox and choose in the corresponding drop-down list the rule that you want to cancel.
Send Magic to
Your Device has the possibility to send a Magic Word over IP to another device in order to remotely trigger an action.
Send magic: specify the Magic Word to use; it can be from 1 to 32 characters long, and it can contain alphanumeric characters.
to: specify the IP address of the destination device
port: specify the port number used to send the Magic Word; the default port number is 52389.