Each Power Outlet individually supports three commands: On, Off, and Restart using following syntax:
M0:Ox=[ON], [OFF], [RESTART]
M0: ID of your Power Switch
Ox: Outlet number of your Power Switch
ON: ON command
OFF: OFF command
RESTART: Restart command
The first command must be preceded by a “?”
Commands can be concatenated using the character “&.”
Commands can be specified in upper case, lower case, or mixed case.
The Hidden Page functionality also allows the user to control peripherals connected to the A-xBus, including all
sensors, Digital I/O Modules, Power Switches, and Current probe.
Example:
If you want to switch OFF Power Outlet #1 and 3, type in:
http://192.168.100.200/hidden.htm?M0:O1=OFF&M0:O3=OFF
Your Web browser will now display:
Hidden Page
21 Jul 2011 02:42:08
Version: 2.3.0.0
M0:O1=Off
M0:O2=On
M0:O3=Off
M0:O4=On
3.1.13 SETTINGS / GROUPS
This page is used to create, modify, and delete groups of power outlets which can be controlled by the PSE544. This
functionality is particularly useful if you have to control the power supply of devices using redundant power supplies.
You can create groups, including multiple power outlets distributed on multiple Power Switch 8XS devices.
FIGURE 3-12: GROUPS
CHAPTER 3: NETWORK SETTINGS