KB-206-1
24
Menu item
Function
Modbus: 16401
0 – 1200 s
Setting ex factory: 450 s
F2+F4⇒PAR⇒CPr⇒COMP
Modbus: 16513
Minimum duration compressor start ⇒ compressor stop
0 – 300 s
Setting ex factory: 60 s
F2+F4⇒PAR⇒CPr⇒OnS
Modbus: 16403
Minimum duration CR II SV activated during modulation
0 – 120 s
Setting ex factory: 1 s
F2+F4⇒PAR⇒CPr⇒OnF
Modbus: 16405
Minimum duration CR II SV not activated during modulation
0 – 120 s
Setting ex factory: 9 s
When modifying the configuration of the condensing
unit (parameter EcM), the parameters OnS and OnF
are adapted by the ECOLITE controller since the con-
figuration of the CR II capacity controllers must cover
different capacity ranges. The following assignment ap-
plies:
Modbus (EcM)
0
1
2
3
Minimum pulse duration (OnS)
1 s
5 s
1 s
1 s
Minimum pause time (OnF)
9 s
5 s
9 s
9 s
Control of the fans – menu FAn:
Menu item
Function
F2+F4⇒PAR⇒FAn⇒SP2
Modbus: 16407
Set point of condensing pressure regulator (without compensation)
10.0 – 80.0°C
Setting ex factory: 30.0°C
F2+F4⇒PAR⇒FAn⇒SP3
Modbus: 16408
Maximum condensing pressure
10.0 – 80.0°C
Setting ex factory: 60.0°C
F2+F4⇒PAR⇒FAn⇒Fbn
Modbus: 16409
Proportional speed band width min. – max. Eco mode
0.0 – 50.0 K
Setting ex factory: 6.0 K
F2+F4⇒PAR⇒FAn⇒Fb2
Modbus: 16410
Proportional speed band width min. – max. LowSound mode
0.0 – 50.0 K
Setting ex factory: 18.0 K
F2+F4⇒PAR⇒FAn⇒FLP
Modbus: 16411
Signal level for min. condenser fan(s) speed
0.0– 7.5 V
Setting ex factory: 0.0 V
F2+F4⇒PAR⇒FAn⇒FMP
Modbus: 16412
Signal level for max. condenser fan(s) speed
0.0– 10.0 V
Setting ex factory: 7.5 V
F2+F4⇒PAR⇒FAn⇒COd
Signal level for start phase of condenser fan(s)