KB-206-1
22
8.1.5
Programming menu
Configuration of the systems and of the ECOLITE
condensing unit – menu CnF:
F2+F4⇒PAR⇒CnF⇒ERt
Modbus: 16384
Refrigerant type in the system
0 = R404A
1 = R22
4 = R134a
8 = R507A
9 = R407A
11 = R407F
12 = R450A
14 = R448A
15 = R513A
16 = R449A
Setting ex factory: 0= R404A
F2+F4⇒PAR⇒CnF⇒EcM
Modbus: 16385
ECOLITE system configuration
0 = no CR II capacity regulator available
1 = 2-cylinder compressor with CR II capacity regulator available
2 = 4-cylinder compressor with 1 CR II capacity regulator available
3 = 4-cylinder compressor with 2 CR II capacity regulators available
Setting ex factory: same as state of delivery of the condensing unit
F2+F4⇒PAR⇒CnF⇒OSP
Modbus: 16443
ECOLITE control function
2 = room temperature control
3 = reserved
4 = suction pressure control
Setting ex factory: 4 = suction pressure control
F2+F4⇒PAR⇒CnF⇒SmU
Modbus: 16386
ECOLITE system of units
0 = Europe (bar / °C) metric
1 = America (PSI / °F) IP
Setting ex factory: 0 = Europe (bar / °C) metric