KB-206-1
19
Display of the status of the digital inputs of the
controller:
Menu item
Function
F4⇒di⇒diL1
Modbus: 8192
(read only)
Status of controller digital input DI01
Safety chain of ECOLITE condensing unit
OFF = compressor off or safety chain was triggered
On = compressor is running, safety chain is OK
F4⇒di⇒diL2
Modbus: 8193
(read only)
Status of controller digital input DI02
Reserve
F4⇒di⇒diL3
Modbus: 8194
(read only)
Status of controller digital input DI03
Reserve
F4⇒di⇒diL4
Modbus: 8195
(read only)
Status of controller digital input DI04
Reserve
F4⇒di⇒diL5
Modbus: 8196
(read only)
Status of controller digital input DI05
Configurable special function 1. Input
OFF = there is no external On command active
On = an external On command is active
F4⇒di⇒diL6
Modbus: 8197
(read only)
Status of controller digital input DI06
Configurable special function 2. Input
OFF = there is no external On command active
On = an external On command is active
Display of the operating times:
Menu item
Function
F4⇒SCr⇒dS1
Modbus: 9012
(read only)
Operating hours counter of CR II solenoid valve 1
Number of days solenoid valve has been operating
F4⇒SCr⇒HS1
Modbus: 9006
(read only)
Operating hours counter of CR II solenoid valve 1
Number of hours solenoid valve has been operating
F4⇒SCr⇒dS2
Modbus: 9014
(read only)
Operating hours counter of CR II solenoid valve 2
Number of days solenoid valve has been operating
F4⇒SCr⇒HS2
Modbus: 9008
(read only)
Operating hours counter of CR II solenoid valve 2
Number of hours solenoid valve has been operating