Fault Analysis
A fault is displayed by the LED being lit and the nature of the fault is indicated on the 7-segment-
display (see Fault Index section).
Basic procedure
– Switch off the power supply to the system
– Check all existing safety edges using an ohmmeter. The resistance value when
the edges are not activated must be around 8.2 kohm
– The resistance must be around 0 ohm when the edges are activated
2.9
Dimensions
130 (5.12")
113.5 (4.47")
60 (2.36")
130 (5.12")
156 (6.14")
100 (3.94")
120 (4.72")
58 (2.28")
148 (5.83")
Fig.13
Fig. 11
Fig. 12
Fig. 14
33 (1.3")
70 (2.76")
83 (3.27")
45 (1.77")
48 (1.89")
19 (0.75")
17 (0.67")
108 (4.25")
34 (1.34")
16 (0.63")
18 (0.71")
35 (1.38")
40 (1.57")
48 (1.89")
23.5 (0.93")
63 (2.48")
INT-50
INT-51
INT-MOB 50
INT-FIX 50
2.8
Start-up
After switching on the device, the operating state is displayed by the green LED being lit and the
flashing dot on the 7-segment-display.
To check the correct safety function every safety edge has to be actuated:
Safety edge actuated
Yellow
7-segment-
OUT1
OUT2
Gate movement
LED
display
None
off
flashing dot
closed
closed
–
at IN1 (mobile, open)
on
“1”
opens
closed
opening stops
at IN2 (mobile, close)
on
“2”
closed
opens
closing stops
at IN3 (stationary, open)
on
“3”
opens
closed
opening stops
at IN4 (stationary, close)
on
“4”
closed
opens
closing stops