!ATTENTION!
There is protection against heat carrier freezing in the Controller, all hooked up pumps
forcefully switch on if outgoing water temperature is lower than 5°С.
4.4 Flameout Time
Controller operation time during burner flameout process is set up in this menu.
To enter menu «Flameout Time» it is required to select item «Service Menu»,
, in the main menu, and press the encoder button, and then enter code
2222
in the
popped up window (Picture 16)
.
Select item «Flameout Time»,
, and press the
encoder button – the Controller will display flameout time setup window (Picture 21).
Picture 21 – Flameout Time Window
To change parameter value, it is required to press the encoder button, the value
will change symbols color to red, set up the needed value and confirm the entered value
by pressing the button.
Value limits, sec.:
200 – 990.
This parameter is changed for selecting time for absolute fuel burnout in the
burner, cease of fuel remnants smoldering and smoke spread in the combustion
chamber.
4.5 Operation Capacity Setup in «Standby» Mode
To set up operation capacity in «Standby» mode it is required to enter code
10**
in the service menu, where «
**
» is operation capacity. For instance, to set up
operation capacity that equals 20% it is required to enter code
1020
.