Biodom 27 d. o. o.
T: +386 8 205 10 86
OIC Hrpelje 4 a, 6240 Kozina
F: +386 5 662 67 57
www.biodom27.si
15
Figure 8
MINIMUM DISTANCES FOR INSTALLING THE VENTILATION GRILLE:
Please refer to the information provided in table 3 for a correct and safe ventilation grille installation. These are
the minimum distances from each air chamber or exhaust. This value may change the configuration of air
pressure. It must match in both directions. This method will help prevent any unnecessary suction of air from
the furnace (ex. opening a window).
Minimum distance of the ventilation grille
1 m
Under
The doors, windows, exhaust, air
chambers, etc.
1 m
Horizontally
0,3 m
Above
2 m
From
The exhaust
Table 3: Minimum distances for air supply
2.5
CONNECTING TO A POWER SOURCE
The furnace must be connected to a power source. Our furnaces have electrical cables suitable for medium
temperatures. If an electrical cable must be substituted (if damaged), please consult with our authorised
technical staff or our experts. Prior to connecting your furnace to a power source, ensure that:
-
the characteristics of the electrical system match the data or specifications indicated on the
identification plate on the furnace;
-
the exhaust system (if metal) must have an operational grounding connection in accordance with
applicable standards and legal provisions. The grounding is imposed by law;
-
the electrical cable must not rise more than 80°C above the ambient temperature. If you wish to
connect the cable directly into the power grid, you must put one bipolar switch or a two polar switch
with a minimum distance of 3 m between contacts. The dimensions for the power overload are
indicated on the identification plate in accordance with applicable standards. The yellow-green
grounding cable must not interrupt the switch. The bipolar switch and inlet must be easily accessible
after the furnace has been positioned into place;
-
if the furnace has not been used for longer periods of time, unplug it from its power source or turn the
switch to »OFF« position (0). In case of breakdown or incorrect operation, immediately turn off the
furnace or turn the switch to »OFF« position (0). Consult our authorised service centre.
T-coupler or bent
component with
inspection hatch