NCR-80 Four-wire 4-20 mA/HART
925-0332 Rev B
6 Set up the sensor with the display and adjustment module
45
Basic settings:
Resets the parameter settings, incl. special parameters, to the default values
of the respective instrument. Any stored false signal suppression or user programmable lineari-
sation curve, as well as the measured value memory, is deleted. Order-related settings are not
taken over into the current parameters after this reset.
The following table shows the scope of the reset function and the default values of the instru-
ment:
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Units
Distance in m
Temperature in °C
Application
Medium: Crushed stones/gravel
Application: Silo
Vessel bottom: Flat
Vessel height/Measuring range: 120 m
Min. adjustment
120 m
Max. adjustment
0.000 m(d)
Damping
0.0 s
Current output mode
Output characteristics: 4 … 20 mA
Failure mode: < 3.6 mA
Current output Min./Max.
Min. current: 3.8 mA
Max. current: 20.5 mA
Display
Displayed value 1
Filling height
Displayed value 2
Temperature
Backlight
Switched off
Additional adjust-
ments
Date/Time
Time format: 24 h
Scaling size
Volume
l
Scaling format
100.00 lin % 100 l
0.00 lin % 0 l
Current output 1 and 2 size
Lin %
Current output 1 and 2 adjustment 100.00 % 100 l
0.00 % 0 l
Linearization
Linear
HART mode
HART address: 0
Loop current mode: Analogue current
output