  Installation, initial start-up and maintenance may only be performed by trained personnel! 

  The device may only be connected to power which complies with the specifications included in the 

technical data and on the serial plate! 

  The device must be disconnected from all sources of power during installation and maintenance work! 

  The device may only be operated under the conditions specified in these operating instructions! 

 

Functions Description: 

 

The MAXIMAT TC4 is a signalling device for up to 4 MAXIMAT C… series overfill inhibitors / leakage sensors with 
optical and acoustic indication in accordance with approval guidelines for overfill inhibitors (ZG-ÜS). If an alarm 
signal is generated by one of the overfill inhibitors or leakage sensors, this can be indicated optically and/or 
acoustically by the MAXIMAT TC4.

 

 

Technical Data: 

 

Supply power:

 

230V AC, 50 to 60Hz, alternatively 24V DC ± 20% 

 

Power consumption:

 

Approx. 6VA / approx. 6W 

 

Ambient temperature: 

-20 to +60°C 

 

Protection per EN 60 529:

 IP65 

 

Inputs:

 

4 each overfill/leakage sensor 

 

1 external reset contact 

 

Outputs:

 

4 floating changeover contacts, assigned to the individual sensors 

 

1 floating changeover contact for group alarms 

 

1 floating changeover contact for the external buzzer 

 

* Note:

  The function test does not replace the operating test specified in ZG-ÜS, section 6.2, which must be conducted on a regular basis at 

least once a year. 

 

Contact rating, output relays: 

250V AC / 115V DC 

 

500VA / 3A 

 

Terminals:

 

Max. wire cross-section of 2.5 sq. mm 

 

 
 
 
 
 
 
 

Safety Precautions: 

Summary of Contents for MAXIMAT TC4

Page 1: ...with optical and acoustic indication in accordance with approval guidelines for overfill inhibitors ZG S If an alarm signal is generated by one of the overfill inhibitors or leakage sensors this can b...

Page 2: ...floating NO contact Channel 1 Channel 2 Channel 3 Channel 4 Alarm Channels 2 20 6 24 Test signal for sensors with T connector 3 21 7 25 Alarm input 4 22 8 26 Sensor supply voltage 5 23 9 27 0 V refere...

Page 3: ...tive sensor equipped with test connection yes no two acoustic signals are generated during testing default setting no interconnected sensors Each time the system test is conducted it can thus be deter...

Page 4: ...8 29 NC C 31 12 30 13 NO NC Summ Alarm Mains 230V 50Hz Signalling device MAXIMAT TC4 18 external Horn NO C NO NC C 34 NC 16 33 14 15 C NO 17 35 36 C NO L N Input Channel TC4 1 2 3 4 Sensor 1 Sensor 3...

Page 5: ...es 32 Alarm 1 NC Alarm 2 Alarm 4 Sensor 2 Sensor 4 6 20 external Reset PB 1 19 22 21 2 3 4 23 5 24 27 7 25 8 26 9 Alarm 3 NC NO C 11 10 28 29 NC C 31 12 30 13 NO NC Summ Alarm Mains 230V 50Hz Signalli...

Page 6: ...10 11 9 8 7 5 4 3 2 1 6 Sensor 3 external Reset PB Sensor 1 Alarm 3 NC NO C Sensor 4 20 Sensor 2 19 22 21 23 24 27 25 26 Alarm 4 28 29 NC C 31 30 NO NC 17 15 14 16 18 Mains 230V 50Hz external Horn C N...

Page 7: ...Alarm 1 NC Alarm 2 Alarm 4 Sensor 2 Sensor 4 6 20 external Reset PB 1 19 22 21 2 3 4 23 5 24 27 7 25 8 26 9 Alarm 3 NC NO C 11 10 28 29 NC C 31 12 30 13 NO NC Summ Alarm Mains 230V 50Hz Signalling dev...

Page 8: ...ctrical Connection floating NC contact Floating NC contacts such as float actuated switches or the BSM501 bistable switch can also be connected to the MAXIMAT TC4 signalling device They re connected i...

Reviews: