O
PERATING
I
NSTRUCTIONS
MAXIMAT
TC4
S
IGNALLING
D
EVICE
BAMO IER GmbH
Pirnaer Str. 24
D-68309 Mannheim, Germany
Phone: +49 (0)621 84224-0
Fax: +49 (0)621 84224-90
www.bamo.de
SU3312a.doc 03/15
2
Technical Data
(continued):
Indication:
4
LEDs
(multi-coloured)
Blinking
red
alarm
pending
Continuous red
alarm acknowledged
Blinking yellow
defective sensor
Continuous yellow
test in progress
Continuous green
sensor active
Dark LED
no sensor connected
1 piezo signal generator: > 70dB (A) at 1m
1 extra-bright flashing LED for group alarm
Controls:
Reset button for acknowledging alarms
Test button for system test
CE Mark:
In accordance with low-voltage directive 2006/95/EC and EMC directive 2004/108/EC
Terminal Assignments:
Terminal Number
Function
L (+)
Mains, 230V AC / +24V DC supply power
N (-)
Mains, 230V AC / 0V DC supply power
1 / 19
External test button (floating NO contact)
Channel 1 Channel 2 Channel 3 Channel 4 Alarm Channels
2
20
6
24
Test signal for sensors with T-connector
3 21 7 25
Alarm
input:
4 22 8 26
Sensor
supply
voltage
5 23 9 27
0
V
reference
potential
13 31 10 28
Output
relay,
NC
contact:
alarm
14 32 11 29
Output
relay,
root: alarm
15 33 12 30
Output
relay,
NO
contact:
alarm
16
Output relay, NC contact:
external buzzer
17
Output relay, root:
external buzzer
18
Output relay, NO contact: external buzzer
34
Output relay, NC contact:
group alarm
35
Output relay, root:
group alarm
36
Output relay, NO contact: group alarm
Note:
The alarm output relays (channels 1 to 4) and the group alarm relay are
pulled in
(closed-circuit current) as long as no alarm is
pending. These relays are released in the event of an overfill /leakage alarm or mains power failure.
In all of the following wiring diagrams, the relays are shown in the
de-energised
state in accordance with the standards (mains power =
OFF)!
The relay for the external buzzer is pulled in when an alarm occurs, and is released after resetting.