NCR-80 Four-wire 4-20 mA/HART
925-0332 Rev B
6 Set up the sensor with the display and adjustment module
40
Setup - Max. Adjustment
Proceed as follows:
1. Select with
[->]
the menu item Max. adjustment and confirm with
[OK]
.
2. Prepare the percentage value for editing with
[OK]
and set the cursor to the requested posi-
tion with
[->]
.
3. Set the requested percentage value with
[
+
]
and save with
[OK]
. The cursor jumps now to
the distance value.
4. For the full vessel, enter the distance value in m matching the percentage value.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to Min. adjustment.
Setup - Min. Adjustment
Proceed as follows:
1. Select with
[->]
the menu item "
Min. adjustment
" and confirm with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the requested position with
[->]
.
3. Set the requested percentage value with
[
+
]
and save with
[OK]
. The cursor jumps now to
the distance value.
4. Enter the suitable distance value in m for the empty vessel (e.g. distance from the sensor to
the vessel bottom) corresponding to the percentage value.