C-Series AS-i Master Module
Safety
3.4.1
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as
equip-
ment under DEMKO Certificate No. 14 ATEX 1413X and IECEx Certificate
No. IECEx UL 14.0112X. Each module is marked II 3G and is suitable for use in
Zone 2 hazardous locations. If you are using the BW3023 in Gas Group IIC
hazardous locations or in ambient temperatures of – 40 °C
Ta
70 °C, you
must use the device in a chassis that has been evaluated as EEx nA IIC T4,
Ex nA IIC T4, or Ex nL IIC T4 equipment.
3.5
Disposal
Caution:
•
Do not disconnect I/O-side wires or connectors unless power has been
switched off or the area is known to be nonhazardous.
•
Do not remove modules unless power has been switched off or the area is
known to be nonhazardous.
•
Substitution of components may impair suitability for Class I, Division 2.
•
For Zone 2 applications, install the system in an enclosure rated to at least
IP54 as defined by IEC 60529 and EN 60529.
Information!
Electronic waste is hazardous waste. Please comply with all local ordinances when
disposing this product!
The device does not contain batteries that need to be removed before disposing it.